Midea MFM-24ARN1-Q Service Manual page 40

Air conditioner floor standing type
Hide thumbs Also See for MFM-24ARN1-Q:
Table of Contents

Advertisement

Floor Standing MFM
When the evaporator coil temp.T2 keeps lower than TE5 for 30 minutes, the compressor and
outdoor fan will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart
up.
Condition 2:
When the evaporator coil temp.T2 keeps lower than TE5-2 for 20 minutes, the compressor and
outdoor fan will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart
up.
Condition 3:
When the evaporator coil temp.T2 keeps lower than TE5-4 for 8 minutes, the compressor and
outdoor fan will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart
up.
Service manual
T2
On
TE6
TE5
Off
T2
On
TE6
TE5-2
Off
T2
On
TE6
TE5-4
Off
DM16-01.01.25en
40

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents