Panasonic CS-ME7CKPG Service Manual page 66

Hide thumbs Also See for CS-ME7CKPG:
Table of Contents

Advertisement

CS-ME7CKPG / CS-ME10CKPG / CS-ME12CKPG / CS-ME14CKPG / CS-ME18CKPG / CU-2E15CBPG / CU-2E18CBPG / CU-3E23CBPG / CU-4E27CBPG
2
HOW TO FIX INSTALLATION PLATE
The mounting wall is strong and solid enough to prevent it from the vibration.
Wall
More than 440 mm
Screw ˇ
Measuring
210 mm
tape
150 mm
The center of installation plate should be at more than 425 mm at right of the wall.
The centre of installation plate should be at more than 440 mm at left of the wall.
The distance from installation plate edge to ceiling should more than 67 mm.
From installation plate left edge to unit's left side is 37 mm.
From installation plate right edge to unit's right is 59 mm.
: For left side piping, piping connection for liquid should be about 95 mm from this line.
: For left side piping, piping connection for gas should be about 155 mm from this line.
: For left side piping, piping connecting cable should be about 800 mm from this line.
1. Mount the installation plate on the wall with 5 screws or more.
(If mounting the unit on the concrete wall consider using anchor bolts.)
• Always mount the installation plate horizontally by aligning the marking-off line with the
thread and using a level gauge.
2. Drill the piping plate hole with ø70 mm hole-core drill.
• Line according to the arrows marked on the lower left and right side of the installation
plate. The meeting point of the extended line is the centre of the hole.Another method
is by putting measuring tape at position as shown in the diagram above. The hole
centre is obtained by measuring the distance namely 150 mm and 120 mm for left and
right hole respectively.
• Drill the piping hole at either the right or the left and the hole should be slightly slanted
to the outdoor side.
3
TO DRILL A HOLE IN THE WALL AND
INSTALL A SLEEVE OF PIPING
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about
15 mm from the wall.
CAUTION
When the wall is hollow, please be
sure to use the sleeve for tube ass'y
to prevent dangers caused by mice
biting the connecting cable.
4. Finish by sealing the sleeve with putty
or caulking compound at the final
stage.
Wall
More than 425 mm
Installation
plate
120 mm
200 mm
Wall
Indoor
Outdoor
15 mm
Sleeve for
tube ass'y
Approx. 5 - 7 mm
Bushing for tube
ass'y
ø70 through hole
Putty or caulking compound