Fujitsu UTP-VX60A Installation Manual page 15

Airstage
Hide thumbs Also See for UTP-VX60A:
Table of Contents

Advertisement

7.5.2. Analog external inputs
Changing the voltage of the signals entered to "analog external inputs" enables you to set
either the operation temperature or the required operation performance.
If using this function, make the following DIP switch settings.
i) Set the "Analog external inputs ON/OFF" setting to "ON".
ii) Set the control item (either the operation temperature or required operation perfor-
mance).
Connected unit
Connected
device
7.5.3. External output
Type-i
DX-kit
No.
Terminal block
internal relay
status
1
ON/OFF SIGNAL
ON (Open)
OFF (Short)
2
ERROR SIGNAL
ON (Open)
OFF (Short)
3
FAN SIGNAL
ON (Open)
OFF (Short)
4
DEFROST SIGNAL ON (Open)
OFF (Short)
5
THERMOSTAT
ON (Open)
ON/OFF SIGNAL
OFF (Short)
6
DRAIN PUMP
OFF
SIGNAL (*1)
ON (AC 230 V)
● Select either of the following two power supply methods.
(Factory setting is Type-i)
Type-i
• Using a power supply from other than the DX-kit (Connected unit, etc.)
• Usable tolerance voltages and currents: AC 220 to 240 V /1A max or
DC 30 V max /1A Max
Type-ii
• Using a power supply from the DX-kit control unit
• Output voltage: Hi DC12V±2V, Lo 0 V / 50 mA max
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
(1) Type-i: Using a power supply from other than the DX-kit (Connected unit, etc.)
Power supply
Connected unit
Connected
device 1
Connected
device 2
Connected
device 3
Connected
device 4
Connected
device 5
Power supply
for drain pump
Drain pump
When using a drain pump, connect relay that is
compatible with AC power supply. (fi eld supply)
Control unit
(DX-kit)
Analog signal
Type-ii
Status
DX-kit output
level
OFF
Stop
ON (DC12V) Operation
OFF
Normal
ON (DC12V) Error
OFF
FAN off
ON (DC12V) FAN on
OFF
Normal
ON (DC12V) Defrosting
OFF
Thermostat Off
ON (DC12V) Thermostat On
Drain pump Off
Drain pump On
AC 220 to 240 V / 1A max
DC 30 V max / 1A max
Control unit (DX-kit)
Relay PC
Terminal
board
1
2
3
4
5
6
• Precautions for Type-i
If connecting a dielectric load such as a relay
coil, etc., to the connected device, make sure to
add a surge protector circuit to the load side as
shown in the diagram.
Power supply
Connected device
Relay
Dielectric load
Surge protector circuit
(2) Type-ii: Using a power supply from the DX-kit control unit
Connected unit
Connected
device 1
Connected
device 2
Connected
device 3
Connected
device 4
Connected
device 5
Power supply
for drain pump
Drain pump
When using a drain pump, connect relay that is
compatible with AC power supply. (fi eld supply)
• If Type-ii is selected, change the wiring as shown in the diagram. (All cables used are
enclosed.)
CNB01
CN800
CN801
CN802
• If connecting an connection cables (accessories) to a terminal, make sure to
match the number of the label affi xed to the cable with the terminal number.
About the cable name and cable color
(a) Connection cable 1:
(a1) Brown, (a2) Red
(a3) Orange, (a4) Yellow
(a5) Green, (a6) Blue
(b) Connection cable 2:
Brown
(c) Connection cable 3:
Brown
(d) Connection cable 4:
Brown
(e) Connection cable 5:
Brown
Control unit (DX-kit)
Relay PC
Terminal
board
32
1
33
Control unit (DX-kit)
Terminal
12 VDC line
32
1
33
34
2
35
36
3
37
38
4
39
40
5
41
6
CNB01
Cable clamps
(a)
(a6)
(a1)
(a2)
(a3)
(a4)
(a5)
(b)
(c)
(d)
(e)
32
33
34
35
36
37
38
39
40
41
En-14

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Utp-vx30aUtp-vx90aUty-vdgx

Table of Contents