8. CONDENSATE DRAINAGE &
CONDENSATE PUMP KIT OPTIONS
In most cooler units once the unit is in place the drain tray MUST slope downwards towards the drain connection. Ensure
that drainline size is equivalent to that of the drain connection and that it has an adequate fall. It is essential that the drain-
line includes a trap, fitted outside the coldroom. Easy disconnection of the drainline will ease cleaning and the replace-
ment of tray heaters and fan sets.
On the KEC and KME the fixings at the rear of the drain tray should be loosened to allow the back of the drain tray to drop
into it's operating position. The drain connection is 1" BSP (M) nylon on the KME and KEC and should be hand tightened
when connected to the drain. Ensure that drainline size is equivalent to that of the drain connection and that it has an
adequate fall.
Condensate pump kit options
The condensate pump option is only available on high temperature units as a factory fitted item or can be bought as a
spare. The Pump kits are to the DSR and LSR units. Please see below fitting instruction guides.
DSR Condensate pump instructions
1.
Remove the end panel of the cooler.
2.
Fit the sensor to the bracket and fit pump and sensor bracket as shown in the diagram, ensuring the brackets are
pushed right down.
3.
Extend the discharge line with 6mmID hose as required.
4.
Insert the Rubber Bung in the sump drain outlet with a blunt instrument.
5.
Connect the electric cable to single phase, 50Hz 230V mains supply.
Note
Clean the Sump and Pump filter 1 week after installation, then at least 4 times a year thereafter.
Pump is fitted with 3 minute (approx) run on timer, activated when float returns to bottom position.
Pump overload must be reset by interrupting the power supply.