Ready To Run; Fuel Requirements And Recommendations; Fuel Consumption - Honeywell 10 kW Owner's Manual

Air-cooled automatic standby generators
Hide thumbs Also See for 10 kW:
Table of Contents

Advertisement

General Information
1-7
READY TO RUN
The "Ready to Run" on the display is ready when all of the following
conditions are true:
3.
The AUTO/OFF/MANUAL switch is set to the AUTO position.
The utility voltage being supplied to the unit is being sensed
by the PCB. If the utility sense voltage is not connected to the
unit or if it is below approximately 150-160 volts AC, then
the system will display the message "No Utility Present". This
indicates that if the AUTO/OFF/MANUAL switch is placed in
the Auto position, the generator will start.
No alarms are present, for example, low oil pressure, high
temperature, etc.
1.8
FUEL REQUIREMENTS AND
RECOMMENDATIONS
With LP gas, use only the vapor withdrawal system. This type of
system usesthe vapors formed above the liquid fuel in the storaqe
tank.
The engine has been fitted with a fuel carburetion system that
meets the specifications of the 1997 California Air Resources
Board for tamper-proof dual fuel systems. The unit will run on
natural gas or LP gas, but it has been factory setto run on natural
gas. Should the primary fuel need to be changed to LP gas, the
fuel system needs to be reconfigured. See the reconfiguring the
Fuel System section for instructions on reconfiguration of the fuel
system.
Recommended fuels should have a Btu content of at least 1,000
Btus per cubic foot for natural gas; or at least 2,520 Btus per
cubic foot for LP gas. Ask the fuel supplier for the Btu content of
the fuel.
Required fuel pressure for natural gas is five (5) inches to seven
(7) inches water column (0.18 to 0.25 psi); and for liquid pro
pane, 10 inches to 12 inches of water column (0.36 to 0.43 psi).
The primary regulator for the propane supply is NOT INCLUDED
with the generator.
NOTE:
All pipe sizing, construction and layout must comply with NFPA
54 for natural gas applications and NFPA 58 for liquid propane
vapor withdrawal applications. Once the generator is installed,
verify that the fuel pressure NEVER drops below five (5) inches
water column for natural gas or 10 inches water column for
liquid propane.
Prior to installation of the generator, the installer should consult
local fuel suppliers or the fire marshal to check codes and regula
tions forproper installation. Local codes will mandate correct rout
ing of gaseous fuel line piping around gardens, shrubs and other
landscaping to prevent any damage.
Special considerations should be given when installing the unit
where local conditions include flooding, tornados, hurricanes,
earthquakes and unstable ground for the flexibility and strength of
piping and their connections.
Use an approved pipe sealant or joint compound on all threaded
fitting.
All installed gaseous fuel piping must be purged and leak tested
prior to initial start-up in accordance with local codes, standards
and regulations.
1.9
FUEL CONSUMPTION
Unit
NG/LP
Nat. Gas
LP Vapor
1/2 Load
Full Load
1/2 Load
Full Load
9/10 kW
102
156
1.25/46
1.93/70
12/12 kW
149
224
1.68/59
2.67/94
15/15 kW
183
261
1.61/59
2.57/94
18/20 kW
206
294
1.89/69
2.90/106
• Natural gas is incubic feet per hour.
"* LP is in gallons perhour/cubic feet perhour.
***Values given are approximate.
NOTE:
Fuel piping "MUST" be based on full load consumption rates
regardless of actual load.
Verify that gas meter is capable of providing enough fuel flow to
include all gaseous household appliances running at maximum
capacity.
1.9.1
BTU FLOW REQUIREMENTS - NATURAL GAS
BTU flow required for each unit based on 1000 BTU per cubic foot.
• 9kW —156,000 BTU/Hour
• 12kW —224,000 BTU/Hour
• 15kW—-261,000 BTU/Hour
• 18kW — 294,000 BTU/Hour
A DANGER!
Gaseous fuels such as natural gas and liquid
^propane (LP) gas are highly explosive. Even
the slightest spark can ignite such fuels and
cause an explosion. No leakage of fuel is
permitted. Natural gas, which is lighter than
air, tends to collect in high areas. LP gas is
heavier than air and tends to settle in low
areas.
NOTE:
A minimum of one approved manual shut-off valve must be
installed in the gaseous fuel supply line. The valve must be eas
ily accessible. Local codes determine the proper location.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

12 kw15 kw20 kw

Table of Contents