Battery; Generator Storage Procedure - Kohler 5ECD Operation Manual

Hide thumbs Also See for 5ECD:
Table of Contents

Advertisement

3.9 Battery

Consult
the
battery
regarding battery care and maintenance.
WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Wear
protective
clothing.
Battery acid may cause
blindness and burn skin.

3.10 Generator Storage Procedure

Keep the craft afloat for generator operation during the
storage procedure. Follow the procedure below when
storing your generator set for a long period (3 months or
more).
1. Start and run the generator set until it reaches
operating temperature or about 15 minutes.
2. Stop the generator set.
3. Change the oil and oil filter; see Section 3.3.4—Oil
Change and Section 3.3.5—Oil Filter Change.
4. Close the seacock and remove the hose at the
seacock. Place the hose in a container having
approximately 3.7-7.5 L (1-2 U.S. gallons) of
coolant/antifreeze. Kohler Co. recommends using
an environmentally friendly potable antifreeze
such as PeakR RV/marine propylene glycol/water
mix or equivalent.
5. Disconnect the lead (#87) to the low seawater
pressure (LWP) switch.
TP-6390 1/06
manufacturer's
instructions
goggles
and
6. With a suitable container at the exhaust outlet, run
the generator set until coolant discharges at the
exhaust outlet or until depleting the coolant
mixture. Do not allow coolant mixture to flow into
waterways.
7. Reconnect the lead (#87) to the low seawater
pressure (LWP) switch.
8. Stop the generator set.
9. Connect the hose to the seacock.
seacock closed.
10. Check the coolant level of the heat exchanger and
add coolant if necessary.
Note: Use antifreeze capable of withstanding the
lowest possible temperatures.
11. Drain fuel completely from the fuel tank.
12. Clean the exterior of the generator set and spread
a light film of oil or silicon spray over any exposed
surfaces that may be subject to rust or corrosion.
13. Keep spark plugs in their holes or seal spark plug
holes with suitable threaded metal plugs.
14. Seal the air inlet, exhaust pipe, and fuel tank cap
with tape.
15. Disconnect and remove the battery. Place the
battery in a warm, dry location for the storage
period. Recharge the battery once a month to
maintain a full charge.
16. Select a well-ventilated (not humid or dusty)
location to store the generator.
17. Cover the entire unit with a dust cover.
Note: Run the generator set once a month
whenever possible.