User Levels; Error Codes - gassero wallcon 115 Installation, User & Service Manual

Wall hug gas fired condensing boiler
Table of Contents

Advertisement

Operat on

USER LEVELS

Certa n user levels only allow certa n user groups to make
sett ngs. To reach the requ red user level, proceed as follows:
operat on
D splay example
1
AUTO
Room temperature
0
4
8
12
16
2
AUTO
T me of day and date
Text3
Operator sect on
0
4
8
12
16
3
AUTO
Enduser
Text3
Comm ss on ng
0
4
8
12
16
4
AUTO
T me of day and date
Text3
Operator sect on
0
4
8
12
16
To reach the OEM level, enter the relevant code.
Sett ng structure for "Enduser"
The example g ven here shows that certa n user levels do not allow certa n
sett ngs to be made. The example shows them h ghl ghted. On the un t,
they are h dden.
Enduser
Comm ss on ng
Heat ng eng neer
T me of day and date
Hours / m nutes
Operator sect on
Month / day
W reless
Year
T me program heat ng c rcu t 1
Start of summer t me
T me program heat ng c rcu t 2
End of summer t me
T me program heat ng c rcu t P
Hol days heat ng c rcu t 1
D agnost cs of consumers
Sett ng structure for "Heat ng eng neer"
Comm ss on ng
Enduser
Heat ng eng neer
T me of day and date
Hours / m nutes
Operator sect on
Month / day
W reless
Year
T me program heat ng c rcu t 1
Start of summer t me
T me program heat ng c rcu t 2
End of summer t me
T me program heat ng c rcu t P
Hol days heat ng c rcu t 1
D agnost cs of consumers
Descr pt on
You see the bas c d splay.
If the bas c d splay s not shown,
press the ESC button to return to t.
Press the OK button.
20
24
You are on user level "Enduser".
Press the Info button for 3 seconds.
20
24
You are g ven a cho ce of user
levels.
Turn the sett ng knob unt l the
requ red user level s reached.
20
24
Press the OK button.
You are now on the requ red user
level.
20
24
OEM
Hours
1...24 h
M nutes
0...60 m n
OEM
Hours
1...24 h
M nutes
0...60 m n
5.3

ERROR CODES

The bo ler control un t supports a 16-b t error code. Older
types of operator un ts m ght d splay 8-b t error codes. If
d fferent from the 16-b t error code, the correspond ng 8-b t
error code s nd cated n parentheses.
Error Code LPB code Descr pt on of error code
10
Outs de temperature, sensor error
20
Bo ler temperature 1, sensor error
25
Bo ler temperature, sol d fuel, sensor error
26
Common flow temperature, sensor error
28
Flue gas temperature, sensor error
30
Flow temperature 1, sensor error
38
Flow temperature, pr mary controller, sensor error
40
Return temperature 1, sensor error
46
Cascade return temperature, sensor error
47
Common return temperature, sensor error
50
DHW temperature 1 sensor error
52
DHW temperature 2 sensor error
54
Flow temperature DHW, sensor error
57
DHW, c rculat on sensor error
60
Room temperature 1, sensor error
65
Room temperature 2, sensor error
68
Room temperature 3, sensor error
70
Storage tank temperature 1 (top), sensor error
71
Storage tank temperature 2 (bottom), sensor error
72
Storage tank temperature 3 (center), sensor error
73
Collector temperature 1, sensor error
78
Water pressure, sensor error
82
LPB address coll s on
83
BSB w re cross-sect onal/no commun cat on
84
BSB w re address coll s on
85
BSB RF commun cat on error
91
Data overrun n EEPROM
98
Extens on module 1, error
99
Extens on module 2, error
100
2 clock t me masters
102
Clock t me master w thout backup
103
Commun cat on error
105
Ma ntenance message
109
Superv s on bo ler temperature
110
STB (SLT) lockout
111
Temperature l m ter safety shutdown
117
Water pressure too h gh
118
Water pressure too low
119
Water pressure sw tch has cut out
121
Flow temperature heat ng c rcu t 1 not reached
122
Flow temperature heat ng c rcu t 2 not reached
125
Max mum bo ler temperature exceeded
126
DHW charg ng temperature not reached
127
DHW leg onella temperature not reached
128
Loss of flame dur ng operat on
129
Wrong a r supply
130
Flue gas temperature l m t exceeded
132
Gas pressure sw tch safety shutdown
133
Safety t me for establ shment of flame exceeded
146
Configurat on error sensor/controll ng elements
151
LMS14... error, nternally
152
Parameter zat on error
153
Un t manually locked
160
Fan speed threshold not reached
162
A r pressure sw tch does not close
164
Flow/pressure sw tch, heat ng c rcu t error
166
A r pressure sw tch error, does not open
169
S therm Pro system error
170
Error water pressure sensor, pr mary s de
171
Alarm contact 1 act ve
172
Alarm contact 2 act ve