System Configuration Menu - Toshiba RAS-107SKV-E5 Technical Handbook

Hide thumbs Also See for RAS-107SKV-E5:
Table of Contents

Advertisement

A number of items are configurable by the wired controller – if an indoor unit without a wired controller requires configuration, it
may be temporarily connected for the procedure to be undertaken. In order to access the men
The indoor units to be configured will be chosen by pressing the UNIT button.
The indoor unit being configured runs its fan and swings its louvers (if possible).
Use SET TEMPERATURE up/down buttons to scroll through the configurable items Use TIMER up/down buttons to choose the
configuration value for Use
SET to confirm configuration value Use CL to undo an incorrect setting (provided that configurable item has not been changed)
Use CHECK to return to normal operation
Item
Description
01
Filter alarm time
02
Dirty environment
03
Network address
Priority Setting for
04
Remote Controller
06
Stratification control
0C
Preheat
0d
Auto mode
0E
SHRMi only
0F
Heat Mode
10
Indoor unit model
11
Indoor unit capacity
12
System number
13
Indoor unit number
14
Group master/slave
15
Temperature Sensor
TEST
Press
+ SET + CL for 4 seconds
Filter sign displayed after selected time has elapsed – or by
external pressure switch (CN70)
Allows filter alarm time to be halved if used in a dirty
environment
When under network control.
0 = Normal
1= Priority (This remote has priority of mode
setting
Increases effective return air temperature setting in heating
mode (0 to 10 K)
Preheat indication on display
Enable or disable Auto mode
Used when multiple indoor units are served via a single FS box
Enable or disable Heat Mode
Must be set when replacing indoor printed circuit board
0000 will generate a (L09) fault
DI/SDI indoor and outdoor units are automatically
addressed, this value may be set manually but it must be
done via the wired controller – on an individual basis.
Settings are 0001 to 0030
Indoor units connected to a common outdoor unit (e.g.
twinned indoor units) will have the same system number -
settings are 0001 to 0064. Automatically allocated – but may
be manually overridden.
Allows selection of master indoor unit within group.
Automatically allocated – but may be manually overridden.
Compensation for missing temperature sensor (split systems
ONLY) – other settings produce F03 fault code

System Configuration Menu

u
Value
0000: Inactive
0001: 150 H
0002: 250 H
0003: 500 H
0004: 1000 H
0005: External switch
0000: Standard 0001: Dirty
0099: Unset
0001 to 0064 available
0000 = Standard 0001 = Priority
0000 to 0010
0000 = available 0001 = unavailable
0000 = available 0001 = unavailable
0000 = normal
0001 = multiple units
0000 = available 0001 = unavailable
0000: 1 way cassette (s models)
0001: 4 way cassette
0002: 2 way cassette
0003: 1 way cassette (y models)
0004: duct (standard)
0005: slim duct
0006: duct (high static)
0007: ceiling
0008: hi wall
0010: console
0011: concealed floor
0014: 4 way cassette (600 x 600)
0013: tall cabinet
0016: fresh air intake
0050: air to air heat exchanger
MM* RAV
MM*
RAV
0001= 007*
0012= 027*
0003= 009*
0013= 030*
0005= 012*
0015= 036*
110*
0006 =
40*
0017= 048*
140*
0007 = 015*
0018= 056*
160*
0009 = 018* 56*
0021= 072*
224*
0011 = 024*
0023= 096*
280*
Air to air heat exchanger
Type
3
0001=
150m
/h
3
0002=
250m
/h
3
0003=
350m
/h
3
0004=
500m
/h
3
0005=
650m
/h
3
0006=
800m
/h
3
0007=
1000m
/h
0001: outdoor unit 1
0002: outdoor unit 2
0001: indoor unit 1
0002: indoor unit 2
0000: single indoor unit
0001: group master
0002: group slave
0022
Default
0004
0000
0099
0000
o
0002; +2
C
(Floor type 000;
0
C)
o
0000
0000 except
SMMS
0000
0000
80*
0099
0099
0099
0022