Digital/Super Digital Inverter Triple Splits - Toshiba RAS-107SKV-E5 Technical Handbook

Hide thumbs Also See for RAS-107SKV-E5:
Table of Contents

Advertisement

Pipe Specifications
*
Total Length
Model (RAV-)
La + Lb
La + Lc
Maximum
SM1603AT-E
50
SP1604AT8-E
SM2244AT8-E
70
SM2804AT8-E
*
Total length of pipe between furthest indoor and outdoor unit.
Maximum distance of Branch pipe from main pipe distributor to furthest indoor unit.
Maximum subtractive distance between pipe branches. Example: -
Example 1
Installed length main pipe L to distributor=38m
Installed length branch a=12m
Installed length branch b=10m
Installed length branch c=12m
Example 2
Installed length main pipe L to distributor=40m
Installed length branch a=15m
Installed length branch b=4m
Installed length branch c=12m
Page 14 of 78
Allowable Piping Lengths (m)
Subtractive
Branch Piping
Piping Length
La, Lb or Lc to
Lb - La
Furthest Indoor
Lb - Lc
Maximum
Maximum
15
20
Example 1
Total pipe length L + a
Subtractive pipe length a – b
Subtractive pipe length c – b
Example 2
Total pipe length L + a
Subtractive pipe length a – b
Subtractive pipe length c – b
Digital / Super Digital Inverter Triple Splits
Height Difference (m)
Indoor Unit - Outdoor Unit (H)
Outdoor Unit
Higher
Maximum
10
30
10
30
Indoor Unit
Indoor Unit
Height
Higher
Difference (∆h)
Maximum
Maximum
30
0.5
30
0.5
38 + 12= 50m
12 - 10=
2m
12 - 10=
2m
40 + 15= 55m
15 -
4= 11m
12 -
4=
8m
Number of
Bent portions
Maximum
or Less
10
10

Advertisement

Table of Contents
loading

Table of Contents