Sequence Of Operation - Lennox 12CHP060 Installation Instructions Manual

12chp series units
Hide thumbs Also See for 12CHP060:
Table of Contents

Advertisement

80°F db / 67°F wb
RETURN AIR
MODEL
PRESSURE
12CHP−024
12CHP−030
12CHP−036
SUCTION
SUCTION
12CHP−042
12CHP−048
12CHP−060
12CHP−024
12CHP−030
12CHP−036
LIQUID
LIQUID
12CHP−042
12CHP−048
12CHP−060

Sequence of Operation

Blower Delay − Cooling
When the thermostat is in the cooling mode, the O circuit is
powered which energizes the reversing valve. Upon cool
ing demand, the thermostat closes circuit R and Y. Closing
R and Y closes unit contactor starting compressor and out
door fan. Thermostat automatically closes R to G circuit
which also brings on the indoor blower at the same time.
Upon satisfying cooling demand, thermostat will open
above circuits and open main contactor, stopping com
pressor and outdoor fan.
Blower Delay − Heating
Upon heating demand the thermostat closes circuit R to Y,
closing unit contactor, starting compressor and outdoor
fan. The reversing valve is not energized in the heating
mode. The thermostat again automatically brings on the in
door blower at the same time. Upon satisfying heating de
mand, the thermostat opens above circuits and stops unit
operation.
Defrost Cycle
If outdoor ambient conditions are such that frost forms on
the outdoor coil, the defrost control monitors the need for
and initiates and terminates defrost cycles as necessary to
maintain system performance. The defrost control is time/
temperature initiated and temperature terminated with a
maximum defrost time (time−out) of 10 minutes. Time be
tween defrost cycles is pre−set at 60 minute intervals at the
factory, but can be field adjusted between 30, 60 or 90 min
utes. See figure 9 for field adjustment of defrost timing.
TABLE 4
NORMAL OPERATING PRESSURES −− COOLING MODE
AIR TEMPERATURE ENTERING OUTDOOR COIL (°F)
65°
70°
75°
80°
78
79
81
82
78
79
81
82
75
77
80
82
80
81
82
84
78
79
80
82
78
79
80
82
140
155
170
184
145
159
173
187
146
161
176
191
155
170
185
200
164
180
196
213
166
182
198
214
82°
85°
90°
95°
83
84
85
87
83
84
85
87
83
84
87
89
84
85
86
87
82
83
84
85
82
83
84
85
190
199
213
228
193
202
216
230
197
206
221
236
206
215
230
245
219
229
245
261
220
229
245
261
The defrost control will initiate a defrost cycle if time period
has elapsed and the defrost sensor detects a temperature
below freezing. At the start of defrost cycle, the defrost con
trol will energize the reversing valve solenoid, shifting the
reversing valve and de−energizing the outdoor fan. The de
frost relay will also close energizing tempering heat for in
creased comfort during defrost , if the unit is so equipped.
The unit will remain in the defrost mode until the defrost
sensor has determined that the frost has been removed
from the coil or a 10 minute time period has elapsed.
DEFROST CONTROL TEST AND
TIME PIN LOCATIONS
JUMPER SHOWN ON T2 PIN
DEFROST
TEST PINS
The defrost control is also equipped with a set of test pins to
aid in troubleshooting of the defrost system. The following
is a brief outline of the testing of the defrost system.
Page 9
100°
105°
110°
89
90
92
89
90
92
91
94
96
88
89
90
86
87
88
86
87
88
243
257
272
244
258
273
251
266
281
260
275
290
277
293
309
277
293
308
DEFROST TIME
PINS
T1 = 30 MINUTES
(T1, T2, T3)
T2 = 60 MINUTES
T3 = 90 MINUTES
FIGURE 9
115°
125°
93
96
93
96
98
103
92
94
90
92
90
92
286
316
287
316
296
326
305
335
326
358
324
356