Installer
Setup
Installer Setup
Number
Name
0250
CPH for second
stage conventional
heat
0260
CPH for third Stage
Heat
0270
CPH for Auxiliary
Heat
0280
Continuous
Backlight
0300
Changeover
0310
Deadband
0320
Temperature
Indication Scale
0330
Daylight Saving
0340
Remote
Temperature
Sensor
0350
Heat Pump
Compressor
Lockout
0360
Heat Pump
Auxiliary Lockout
0535
Temporary
Occupied Duration
Limit
0540
Number of Periods 4
0580
Minimum
Compressor Off
Time
0600
Heat Temperature
Range Stops
0610
Cool Temperature
Range Stops
Table 4. Installer Setup Menu. (Continued)
Default
Setting
All Settings
9
1-12
9
1-12
9
1-12
0
0—No
1—Yes
1
0—Manual
1—Auto
3°F
2 (1.5)—2°F (1.5°C)
(2°C)
3 (2.0)—3°F (2.0°C)
4 (2.5)—4°F (2.5°C)
5 (3.0)—5°F (3.0°C)
6 (3.5)—6°F (3.5°C)
7 (4.0)—7°F (4.0°C)
8 (4.5)—8°F (4.5°C)
9 (5.0)—9°F (5.0°C)
0
0—°F
1—°C
2
0—Disabled
1—Enabled (US 1987)
2—Enabled (US 2007)
3—Enabled (Europe)
0
0—None
1—Outdoor for Display
2—Outdoor for Control
3—Remote 10K Indoor
4—Remote 20K Indoor
0
0—None
15(-9.5)—15°F (-9.5°C)
20(-6.5)—20°F (-6.5°C)
25(-4.0)—25°F (-4.0°C)
30(-1.0)—30°F (-1.0°C)
35 (1.5)—35°F (1.5°C)
40 (4.5)—40°F (4.5°C)
45 (7.0)—45°F (7.0°C)
0
0—None
40(4.5) — 40°F (4.5°C)
45(7.0) — 45°F (7.0°C)
50(10.0)—50°F (10.0°C)
55(13.0)—55°F (13.0°C)
60(15.5)—60°F (15.5°C)
3
0—no duration
1—one hour
2—two hours
3—three hours
4—four hours
2—2 Periods
4—4 Periods
5
0—Off
2—2 minutes
3—3 minutes
4—4 minutes
5—5 minutes
90
40 to 90°F (4 to 32°C)
50
50 to 99°F (10 to 37°C)
TB7220U ULTRASTAT PROGRAMMABLE THERMOSTAT
Only shown for conventional system with at least
two stages conventional heat or 2H/1C heat pump
(ISU 0170).
Only shown for 3H/2C heat pump system
(ISU 0170).
Only shown for multi-stage heat pump system with
more heat than cool stages (ISU 0170).
Always shown. If AC power not present the option
is overridden and normal backlight operation
occurs.
Only shown for system with both heat and cool
stages (ISU 0170).
Only shown for Auto Changeover system
(ISU 0300).
Averaging would not include on-board sensor. It is
accomplished by series/parallel combinations.
2 applies only to Heat Pump applications (allowing
compressor lockout while displaying temperature).
Only shown for heat pump systems with more heat
stages than cool (ISU 0170) and remote outdoor
control sensor (ISU 0340 at 2).
Requires a deadband between this and the
Auxiliary Lockout (ISU 360).
Only shown for heat pump systems with more heat
stages than cool (ISU 0170) and remote outdoor
control sensor (ISU 0340 at 2).
Requires a deadband between this and the Heat
Pump Compressor Lockout (ISU 350).
0 means no limit.
Does not appear with Non-programmable chosen
(ISU 0160 at 0).
Applies to all days of the week.
Only shown if system has cool stages (ISU 0170).
Only shown if system has heat stages (ISU 0170).
Only shown if system has cool stages (ISU 0170).
11