Siemens RDE100.1DHW Operating Instructions page 4

Room thermostat

Advertisement

Do you want to change the parameters?
+
If you want to change control parameters, proceed as
follows:
ok
+
Press
and
mode
Release them and parameter "P01" is displayed
on the bottom segment
+
Press
or
needs to be adjusted
Press ok to select this parameter
+
Press
or
Press ok to confirm the adjusted value
Press mode to exit the parameters without
saving or wait for the program to exit
automatically
Parameter list
Parameter
Description
no.
P01
Time format
P02
Selection of ° C or ° F
P03
Standard
temperature display
P04
Temperature sensor
calibration
P06
Comfort setpoint lock
P08
Economy setpoint
lock
P09
Buzzer
P10
Show frost protection
icon
P11
Time switch type for
autotimer and DHW
P12
Periodic pump run
P13
DHW timer bar
timeout
P21
Button scanning rate
for the capacitive
buttons
Note: a higher
scanning rate means
shorter battery life.
P22
Reload factory
settings
P23
Software version
information
4/4
Operating Instructions
simultaneously for 5 seconds
to scroll to the parameter that
to adjust the value
Setting range (default)
1 = 24:00 hours (default)
2 = 12:00 AM/PM
1 = ° C (default)
2 = ° F
1 = room temperature (default)
2 = setpoint
-3...3 ° C
Step 0.5 ° C
(-6...6 ° F, step 1 ° F)
Default: 0 ° C
0 = OFF (default)
1 = ON
locked according to
setting in permanent
temperature setpoint
0 = OFF (default)
1 = ON
locked according to
setting in permanent
temperature setpoint
0 = OFF
1 = ON (default)
0 = OFF (default)
1 = ON
0 = individual Days (default)
1= all 7 days
2= 5/2 days
0 = OFF (default)
1 = ON
00 = no DHW bar
1 = 1 minute (default)
2 = 2 minutes
Adjustable range 0 to 15
minutes
0.2 = 0.25 s
0.5 = 0.5 s
1.0 = 1.0 s (default)
1.5 = 1.5 s
0 = OFF (default)
1 = reload
No adjustment possible
CB1B1423en_01 / 2013-03-08