Siemens RDE100.1RF Operating Instructions page 4

Wireless

Advertisement

Do you want to lock the buttons?
Mode
Press and hold Mode for at least 7 seconds to
activate a button lock. Repeat to unlock.
The unit operates normally when the buttons
are locked, but changes cannot be made.
Do you want to pair transmitter and
receiver?
Please refer to the instructions that come with
+
the receiver.
Learn
Mode
Do you want to change the parameters?
If you want to change control parameters,
+
proceed as follows:
+
Press
and
Ok
seconds
Mode
Release the buttons and parameter
P01 is displayed on the bottom
segment
+
Press
or
that needs to be changed
Press Ok to select the parameter
+
Press
or
Press Ok to confirm the changed value
Press Mode to exit the parameters
without saving or wait for the program
to exit automatically
4/4
Operating Instructions
simultaneously for 5
to scroll to the parameter
to change the value
CB1B1432en_01 / 2013-07-05
Parameter list
Parameter
Description
no.
P01
Time format
P02
Selection of °C or
°F
P03
Standard
temperature display
P04
Temperature
sensor calibration
P06
Comfort setpoint
lock
P08
Economy setpoint
lock
P09
Buzzer
P10
Show frost
protection icon
P11
Time switch type
for Auto Timer
P12
Periodic pump run
P14
X1 external input
P15
Temperature
limitation
P16
Max. limitation
temperature for
floor heating
P17
Window contact
features
P19
Sequential number
of room unit
P20
RF learn
P21
Scanning rate for
the capacitive
buttons
Note: Shorter
scanning rate
means shorter
battery life
P22
Reload factory
settings
P23
Software version
information
Siemens Building Technologies
Setting range
(default)
1 = 24:00 hours
(default)
2 = 12:00 am/pm
1 = °C (default)
2 = °F
1 = room
temperature
(default)
2 = setpoint
-3...3 °C
Step 0.5 °C
(-6...6 °F, step 1 °F)
Default: 0 °C
0 = OFF (default)
1 = ON  locked
according to setting
in permanent
temperature setpoint
0 = OFF (default)
1 = ON  locked
according to setting
in permanent
temperature setpoint
0 = OFF
1 = ON (default)
0 = OFF (default)
1 = ON
0 = individual days
(default)
1= all 7 days
2= 5-2 days
0 = OFF (default)
1 = ON
0 = no input (default)
1 = external sensor
2 = digital input
0 = OFF (default)
1 = ON
35...60 °C, step 1 °C
or
95...140 °F, step 1 °F
Default: 55 °C
0 = normally open
contact (default)
1 = normally closed
contact
0 = no display of
zone (RF off)
1 = zone number 1
(for standard RF)
(default)
...
6 = zone number 6
0 = OFF (default)
1 = ON
0.2 = 0.25 s
0.5 = 0.5 s
1.0 = 1.0 s (default)
1.5 = 1.5 s
0 = OFF (default)
1 = reload
No adjustment
possible