Static Pressure Compensation Mode - LG MULTI V ARUN***CTE4 Installation Manual

Table of Contents

Advertisement

Static pressure compensation mode

This function secures the air flow rate of ODU, in case static pressure has been applied like using
duct at fan discharge of ODU.
Static pressure compensation mode setting method
FAN Maximum RPM of each step (575V Model)
Capacity
Max. RPM
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn2" Push the '●' button
Select the Option using '▶', '◀' Button :
"op1~op3" Push the '●' button
Start the Static pressure compensation mode :
Save the selected option value in EEPROM
Standard
op1
op2
op3
8HP(6Ton)
10~14HP,18HP(8~14Ton)
730
800
820
850
TEST RUN
71
950
1020
1050
1110

Advertisement