Total pipe length = A+B+C+a+b+c+d+e ≤ 1000m(3281ft)
Longest pipe length
L
A+B+b ≤ 150m(492ft)[200m(656ft)**] A+B+b ≤ 175m(574ft)[225m(738ft)**]
Longest pipe length after 1st branch
B+b ≤ 40m(131ft)[90m(295ft)**]
Difference in height (Outdoor Unit ÷ Indoor Unit)
H
H ≤ 110m(361ft)
Difference in height (Indoor Unit ÷ Indoor Unit)
h
h ≤ 40m(131ft)
Difference in height (Outdoor Unit ÷ Outdoor Unit)
h1
h1 ≤ 5m(16ft)
• * : Assume equivalent piping length of Y branch to be 0.5m(1.64ft), that of header to be
1m(3.28ft), calculation purpose.
• ** : To apply Conditional Application
• Indoor Unit should be installed at lower position than the header.
WARNING
!
• It is recommended that difference of piping length for pipes connected to the Indoor Unit
is minimized. Performance difference between Indoor Units may occur.
• When the any one (or both ) of below conditions are satisfied, the diameter of main pipe
(A) must be increased according to below table.
- The equivalent length between outdoor unit and the farthest indoor unit is 90m(295ft) or
more (Liquid and Gas pipes are increased)
- The level difference (Outdoor unit ÷ Indoor unit) is 50m(164ft) or more (Only liquid pipe
is increased)
Refrigerant pipe diameter from outdoor unit to first branch. (A)
Upward Outdoor
unit
Standard Pipe Diameter
total capacity
Liquid pipe
Ton
HP
[mm(inch)]
6
8
Ø 9.52(3/8)
8
10
Ø 9.52(3/8)
10 ~ 12 12 ~ 14 Ø 12.7(1/2) Ø 28.58(1-1/8) Ø 15.88(5/8) not increased Ø 15.88(5/8) not increased
14~18 18~22 Ø 15.88(5/8) Ø 28.58(1-1/8) Ø 19.05(3/4) Ø 31.8(1-1/4) Ø 19.05(3/4) not increased
20
24
Ø 15.88(5/8) Ø 34.9(1-3/8) Ø 19.05(3/4) not increased Ø 19.05(3/4) not increased
22 ~ 28 26 ~ 34 Ø 19.05(3/4) Ø 34.9(1-3/8)
30
36
Ø 19.05(3/4) Ø 41.3(1-5/8)
• If the step up size is not available, you can not select the next higher size available.
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
When pipe length is 90m or
more from ODU to 1st branch
Gas pipe
Liquid pipe
[mm(inch)]
[mm(inch)]
Ø 19.05(3/4)
Ø 12.7(1/2)
Ø 22.2(7/8)
Ø 12.7(1/2)
Ø 22.2(7/8)
Ø 22.2(7/8)
*Equivalent pipe length
Increased Pipe Diameter
When level difference is 50m
Gas pipe
Liquid pipe
[mm(inch)]
[mm(inch)]
Ø 22.2(7/8)
Ø 12.7(1/2)
Ø 25.4(1)
Ø 12.7(1/2)
Ø 38.1(1-1/2)
Ø 22.2(7/8)
not increased
Ø 22.2(7/8)
35
or more
Gas pipe
[mm(inch)]
not increased
not increased
not increased
not increased

Advertisement