Worked example of discharge pipe sizing
Fig. 5: shows a G1/2 temperature relief valve with a
discharge pipe (D2) having 4 No. elbows and length of
7m from the tundish to the point of discharge.
From Table 3:
Maximum resistance allowed for a straight length of
22mm copper discharge pipe (D2) from a G1/2
temperature relief valve is 9.0m.
Subtract the resistance for 4 No. 22mm elbows at 0.8m
each = 3.2m
Therefore the permitted length equates to: 5.8m
5.8m is less than the actual length of 7m therefore
calculate the next largest size.
Maximum resistance allowed for a straight length of
28mm pipe (D2) from a G1/2 temperature relief valves
equates to 18m.
Subtract the resistance of 4 No. 28mm elbows at 1.0m
each = 4.0m
Therefore the maximum permitted length equates to:
14m
As the actual length is 7m, a 28mm (D2) copper pipe
will be satisfactory.
WARNINGS:
Under no circumstances should the factory
fi tted temperature/pressure relief valve be
removed other than by a competent
person. To do so will invalidate any
guarantee or claim.
The cold water combination valve assembly
must be fi tted on the mains water supply to
the CENTERSTORE cylinder.
No control or safety valves should be tampered
with or used for any other purpose.
The discharge pipe should not be blocked or
used for any other purpose.
The tundish should not be located adjacent
to any electrical components.