1. Short description
TCW122B-CM is an Ethernet controller, based on TCW122 hardware. It has 2 digital and 2 analog
inputs, 1-Wire interface for up to 2 temperature/humidity sensors and 2 relays with NO/NC contacts.
The relays can be activated either remotely (WEB, SNMP etc.) or locally - from status of monitored
parameter (temperature, humidity, analog voltage and dry contact). Only one parameter can manage
the relay at the same time, but for every parameter can be sent e-mail/SNMP trap for alert conditions.
TCW122B-CM is suitable for environmental monitoring and local control of heater/coolers,
industrial and building automation, data acquisition systems, general remote control and monitoring.
2. Features
10 Mb Ethernet connectivity;
Password protected, web based configuration and control;
2 digital inputs with " dry contact" and "logic level" modes;
2 analog inputs with 0 to 60VDC range;
2 relays with NO and NC contacts;
Long 1-Wire support for up to 2 temperature (TST1XX) or temperature/humidity (TSH2xx)
sensors;
SNMP v.1 support;
SNMP traps and/or e-mail sending for alert conditions;
SMTP with authentication (SSL is not supported);
HTTP and SNMP port changing;
HTTP and XML API commands;
Remote firmware update.
TCW122B-CM_R1
( Firmware version 2.xx )
Ethernet controller
(Firmware version 2.xx)
User manual
TCW122B-CM
Page 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TCW122B-CM and is the answer not in the manual?

Questions and answers

Summary of Contents for Teracom TCW122B-CM

  • Page 1 User manual 1. Short description TCW122B-CM is an Ethernet controller, based on TCW122 hardware. It has 2 digital and 2 analog inputs, 1-Wire interface for up to 2 temperature/humidity sensors and 2 relays with NO/NC contacts. The relays can be activated either remotely (WEB, SNMP etc.) or locally - from status of monitored parameter (temperature, humidity, analog voltage and dry contact).
  • Page 2: Technical Parameters

    3. Technical parameters Supply voltage, VDC 12±2 Maximum current consumption (with both relays ON), mA Weight, g Dimensions, mm 107 x 72 x 32 Operating temperature, °C 0 to +40 Maximum humidity in 0 to 31°C range, %RH Maximum humidity at 40°C (linear slope between 31-40°C), %RH Minimum high level input voltage for digital inputs, VDC +2.5 Maximum low level input voltage for digital inputs, VDC...
  • Page 3: Environment Information

    Joint part with external component shall have space for attachment/removal of the cable after installation. Teracom does not guarantee successful operation of the product if the product was used under conditions deviating from the product specifications.
  • Page 4: Maintenance

    Installation consists of mounting the device, connecting to an IP network, connecting inputs and outputs, providing power and configuring via a web browser. TCW122B-CM can be wall or flat, not flammable surface mounted, in a clean and dry location room. Ventilation is recommended for installations where ambient air temperature is expected to be high.
  • Page 5 11.1 Login page After opening the Login page, authorization data must be entered (by default username=admin , password=admin). It is recommended to change the username and password to prevent unauthorized access to the controller. The controller supports one active session – only one user can operate the device. If another user tries to login, the message “Someone’s logged in”...
  • Page 6 11.3 I/O setup page I/O settings can be made here. For temperature, humidity and analog value MIN, MAX and HISTERESYS values can be set. These values define the thresholds for all monitored parameters. When the measured value goes out of range SNMP trap or e-mail (if enabled) will be sent. Leaving range is considered when the parameter goes lower than MIN values or higher than MAX.
  • Page 7 Mail server [IP:port] – domain or IP address and port of SMTP mail server;  E-mail – sender e-mail;  Username and Password – authentication details for mail server. When configuring the Mail server, note that TCW122B-CM does not support SSL ( Secure Socket Layer). TCW122B-CM_R2 ( Firmware version 2.xx ) Page 7...
  • Page 8 15 “XML and HTTP API commands”. 11.5 SNMP Setup page TCW122B-CM supports SNMP v.1. This enables the device to be part of large monitoring and control networks. The possible settings for “SNMP” section are: ...
  • Page 9: Application Examples

    The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Teracom Ltd. cannot assume responsibility or liability for actual use based on the examples and diagrams.
  • Page 10 A relay contact of monitored device is connected to the digital input. When an event occurs – the controller can sends an e-mail and/or SNMP trap. 12.4. Data acquisition The TCW122B-CM can be used in Data Acquisition Systems (DAQ). The device uses SNMP v.1 protocol for communication with monitoring and management software applications. 13. 1-Wire Bus 1-Wire is a registered trademark of Maxim Integrated Products, Inc.
  • Page 11 14. Control and monitoring using SNMP TCW122B-CM can be configured and monitored through SNMP (Simple Network Management Protocol). This could be done using every SNMP v.1 compatible program. Parameters that can be changed, are grouped according to their functions in the tables below. To obtain a valid OID number it is necessary to replace the “x”...
  • Page 12 14.6. Setup -> oneWireSensor2 -> temperature2 Name Access Description Syntax x.2.6.1.1.0 temperature2Min read-write Temperature2 range (min. value) INTEGER (-400..1250) x.2.6.1.2.0 temperature2Max read-write Temperature2 range (max. value) INTEGER (-400..1250) x.2.6.1.3.0 temperature2Hyst read-write Hysteresis INTEGER (0..1250) x.2.6.1.4.0 temperature2Action read-write Temperature2 action INTEGER { noAction(0), sendMail(1) } 14.7.
  • Page 13: Monitor&Control

    XML is often preferred choice when it comes to M2M communication and system integration. The monitored values are transmitted in status.xml file that can be easily processed by software applications. Below is the structure of the status.xml file : <Monitor> <Device>TCW122B-CM</Device> Device Type <FW>tcw122-cm_v1.01</FW> Firmware version <DigitalInput1>OPEN</DigitalInput1>...
  • Page 14: Factory Default Settings

    16. Factory default settings TCW122B-CM can be restored to its original factory default settings, following the steps below:  Turn off the power supply;  Press and hold the RESET button then turn on the power supply;...
  • Page 15: Firmware Update

    17. Firmware update TCW122B-CM supports remote firmware update. To update the device follow the steps below: Go to www.teracom.cc and download the latest firmware version file (v2.XX.cod) from TCW122B-CM product page; Go to the device login page, enter user name and password and press the “Login” button;...
  • Page 16 TCW122B-CM_R2 ( Firmware version 2.xx ) Page 16...

Table of Contents