RX3i Ethernet NIU
Serial Cable Lengths and Shielding
The connection from a NIU serial port COM1 to the serial
port on a computer or other serial device requires a serial
cable. This connection can be made with the
IC200CBL001 cable kit or you can build cables to fit the
needs of your particular application. See the Ethernet NIU
Reference Manual, GFK-2296 for more information on
serial communications, cables, and converters.
Maximum cable lengths (the total length from the NIU to
the last device attached to the serial cable) are:
Port 1 (R
S-232) – 15 meters (50 ft.), shielded cable
optional
Port 2 (RS-485) – 1200 meters (4000 ft.), shielded
red
cable requi

LED Operation

The following table lists the NIU LED functions during normal operation (after initialization sequence is complete).
On
NIU OK
NIU OK
NIU OK , OUTPUTS ENABLED, NIU SCANNING I/O
Blinking in unison
NIU OK Blinking. Other LEDs off.
NIU SCANNING I/O
NIU SCANNING I/O
OUTPUTS ENABLED
OUTPUTS ENABLED
I/O FORCE
BATTERY
BATTERY
SYSTEM FAULT On
COM1
COM2
LED State
Blinking
Off
On
Off
On
Off
On
Off
On
Blinking
On
Blinking
Blinking
Configuration
The RX3i NIU and I/O system is configured with Machine
Edition Logic Developer programming software.
Machine Edition automatically populates the Ethernet NIU
target in the folder with the required application code blocks,
and partially prepoulates the EGD Exchanges that are
required for ENIU operation.
The NIU verifies the actual module and backplane
configuration at power-up and periodically during operation.
The actual configuration must be the same as the
programmed configuration. Deviations are reported to the NIU
alarm processor function for configured fault response. Refer
to the Proficy Machine Edition Logic Developer Getting
Started Manual, GFK-1918 and the online help for a
description of configuration functions.
NIU Operating State
NIU has passed its powerup diagnostics and is
functioning properly.
NIU problem. RUN and OUTPUTS ENABLED LEDs
may be blinking in an error code pattern, which can be
used by technical support for troubleshooting. This
condition and any error codes should be reported to
your technical support representative.
NIU is in boot mode and is waiting for a firmware update
through serial port.
CPU in Stop/Halt state; possible watchdog timer fault.
Cycle power in Stop mode and refer to fault tables.
NIU is in Run mode
NIU is in Stop mode.
Output scan is enabled.
Output scan is disabled.
Override is active on a bit reference.
Battery is low.
Battery is dead or not attached.
NIU is in Stop/Faulted or Stop/Halted mode.
Signal activity on port.
5
GFK-2419M