STANDARD WALL-MOUNTED
Figure 34: Sound Pressure Measurement Location.
3.3 ft.
Microphone
Table 29: Standard Wall-Mounted Sound Pressure Levels.
Model
ARNU053SBL4
ARNU073SBL4
ARNU093SBL4
ARNU123SBL4
ARNU153SBL4
ARNU183SCL4
ARNU243SCL4
ARNU303SVA4
ARNU363SVA4
Figure 35: ARNU053SBL4, ARNU073SBL4, and ARNU093SBL4 Sound Pressure Level Diagrams.
ARNU053SBL4
52 | STANDARD
• Measurements are taken 3.3 ft away from the front of the unit.
• Sound pressure levels are measured in dB(A) with a tolerance of ±3.
• Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
Operating Conditions:
• Power source: 220V/60 Hz
• Sound level will vary depending on a range of factors including the construction
(acoustic absorption coefficient) of a particular room in which the unit was installed.
3.3 ft.
High Fan Speed
30.0
32.0
34.0
40.0
42.0
40.0
45.0
49.0
52.0
©
Sound Pressure Levels dB(A)
Medium Fan Speed
29.0
30.0
31.0
34.0
40.0
35.0
40.0
44.0
47.0
ARNU073SBL4
Low Fan Speed
28.0
28.0
30.0
31.0
34.0
31.0
35.0
42.0
43.0
ARNU093SBL4