Johnson Controls TEC2645-4 Technical Bulletin

Johnson Controls TEC2645-4 Technical Bulletin

Network temperature and humidity controllers

Advertisement

TEC Series BACnet® MS/TP Network Temperature and
Humidity Controllers
Technical Bulletin
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Connecting the MS/TP Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
MS/TP Controller Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Adding a Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Adding Point Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
MS/TP Bus Objects Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
TEC2645-4 Thermostat Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
TEC2601-4 and TEC2601-4+PIR Thermostat Controllers . . . . . . . . . . . . . . . . . . . . . . . 26
TEC2602-4 and TEC2602-4+PIR Thermostat Controllers . . . . . . . . . . . . . . . . . . . . . . . 29
TEC2603-4 and TEC2603-4+PIR Thermostat Controllers . . . . . . . . . . . . . . . . . . . . . . . 33
TEC2604-4 and TEC2604-4+PIR Thermostat Controllers . . . . . . . . . . . . . . . . . . . . . . . 41
TEC262xx-0+PIR Thermostat Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Refer to the
TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers
QuickLIT Web site
for the most up-to-date version of this document.
Code No. LIT-12011592
Issued March 4, 2013
Supersedes May 13, 2011
Technical Bulletin
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TEC2645-4 and is the answer not in the manual?

Questions and answers

Summary of Contents for Johnson Controls TEC2645-4

  • Page 1: Table Of Contents

    TEC2645-4 Thermostat Controller ........
  • Page 2 TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin...
  • Page 3: Introduction

    TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin Introduction This document describes how to configure the various TEC Series Network Temperature and Humidity Controllers for BACnet® Master-Slave/Token-Passing (MS/TP) networked applications, including how to: • connect to the MS/TP Bus and map a controller into a Network Automation Engine (NAE) •...
  • Page 4: Related Documentation

    Networked Thermostat Controllers with Dehumidification Capability, Benefits of the Fan Control, and Occupancy Sensing Capability Product Bulletin TEC Series BACnet TEC2645-4 BACnet MS/TP Networked Thermostat Controller with LIT-12011586 MS/TP Network Single Proportional Output and One-Speed Fan Control Product Temperature and...
  • Page 5 24-9890-1001 TEC Series BACnet Fan Control, and Occupancy Sensing Capability Installation MS/TP Network Instructions Temperature and TEC2645-4 BACnet MS/TP Networked Thermostat Controller with Part No. Humidity Controller Single Proportional Output and One-Speed Fan Control Installation 24-9890-1028 Instructions TEC26x7-4 and TEC26x7-4+PIR Series BACnet MS/TP Networked Part No.
  • Page 6: Product Overview

    Product Overview The technologically advanced TEC Series Temperature and Humidity Controllers feature a Building Automation System (BAS) BACnet MS/TP communication capability that enables remote monitoring and programming for efficient space temperature control. The TEC Series Temperature and Humidity Controllers feature an intuitive user interface with backlit display that makes setup and operation quick and easy.
  • Page 7 The MS/TP Bus requires proper termination and biasing at each end of a segment (a segment is a physically continuous length of wire). Because controllers are not equipped with end-of-line termination, a Johnson Controls® MS-BACEOL-0 End-of-Line Terminator (ordered separately) or similar device is recommended to provide this end-of-line termination.
  • Page 8: Ms/Tp Controller Mapping

    MS/TP Controller Mapping Preparation Before mapping a TEC Series BACnet MS/TP Network Temperature and Humidity Controller into an NAE: 1. Decide which point objects within the controller need to be mapped. Only map the point objects that need to be viewed on a regular basis because excessive mapping lowers system performance.
  • Page 9: Adding Point Objects

    Assisted Definition using Auto Discovery is the easiest way to add a new controller online; however, this method requires that the controller to be added is connected and ready to communicate. IMPORTANT: Because some of the objects may not directly correlate to a previous version (TEC26xx-2), you must rediscover all point objects for the TEC26xx-4 version.
  • Page 10: Troubleshooting

    Troubleshooting Table 2: Troubleshooting Details Symptom Probable Causes Multiple Symptoms Excessive bus errors may be occurring. A device may have been added or changed with a duplicate address (may not be the same address as some devices having problems, and may have happened sometime before the problem was noticed).
  • Page 11: Ms/Tp Bus Objects Tables

    MS/TP Bus Objects Tables TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controllers Table 3: TEC26x6(H)-4 and TEC26x6H-4+PIR Series MS/TP Bus Objects (Part 1 of 7) Point Name Thermostat Point Range (Type/Address) 1, 2 AV 7 -40.0°F/-40.0°C to Room Temp 122.0°F/50.0°C BV 8 0 = Normal Room Temp Override 1 = Override...
  • Page 12 Table 3: TEC26x6(H)-4 and TEC26x6H-4+PIR Series MS/TP Bus Objects (Part 2 of 7) Point Name Thermostat Point Range (Type/Address) MSV 17 • If Fan Mode Sequence is set at 1, then: Fan Mode 1 = Low 2 = Med 3 = High •...
  • Page 13 Table 3: TEC26x6(H)-4 and TEC26x6H-4+PIR Series MS/TP Bus Objects (Part 3 of 7) Point Name Thermostat Point Range (Type/Address) MSV 28 1 = Off 2, 5 Fan Status 2 = Low 3 = Med 4 = High BI 29 0 = Deactivated BI1 Status 1 = Activated 5, 6...
  • Page 14 Table 3: TEC26x6(H)-4 and TEC26x6H-4+PIR Series MS/TP Bus Objects (Part 4 of 7) Point Name Thermostat Point Range (Type/Address) MSV 46 1 = None BI1 Configuration 2 = Rem NSB 3 = Motion NO 4 = Motion NC 5 = Window MSV 47 1 = None BI2 Configuration...
  • Page 15 Table 3: TEC26x6(H)-4 and TEC26x6H-4+PIR Series MS/TP Bus Objects (Part 5 of 7) Point Name Thermostat Point Range (Type/Address) MSV 62 1 = 0 Hours Temporary Occupancy Time 2 = 1 Hour 3 = 2 Hours 4 = 3 Hours 5 = 4 Hours 6 = 5 Hours 7 = 6 Hours...
  • Page 16 Table 3: TEC26x6(H)-4 and TEC26x6H-4+PIR Series MS/TP Bus Objects (Part 6 of 7) Point Name Thermostat Point Range (Type/Address) Dehumidification Hysteresis AV 72 2 to 20% RH (TEC2636-4, TEC2636H-4, TEC2636H-4+PIR, TEC2656-4, TEC2656H-4, and TEC2656H-4+PIR Models) Dehumidification MaxCool AV 73 20 to 100% RH (TEC2636-4, TEC2636H-4, TEC2636H-4+PIR, TEC2656-4, TEC2656H-4, and...
  • Page 17 Table 3: TEC26x6(H)-4 and TEC26x6H-4+PIR Series MS/TP Bus Objects (Part 7 of 7) Point Name Thermostat Point Range (Type/Address) BV 78 0 = Direct Acting Direct/Reverse Acting 1 = Reverse Acting (TEC2646-4, TEC2646H-4, TEC2646H-4+PIR, TEC2656-4, TEC2656H-4, TEC2656-4+PIR, and TEC2656H-4+PIR Models) 7, 8 Device 73aaa TEC26x6-aaa...
  • Page 18: Tec2645-4 Thermostat Controller

    TEC2645-4 Thermostat Controller Table 4: TEC2645-4 MS/TP Bus Objects (Part 1 of 4) Point Name Thermostat Point Range (Type/Address) 1, 2 AV 7 -40.0°F/-40.0°C to Room Temp 122.0°F/50.0°C BV 8 0 = Normal Room Temp Override 1 = Override 3, 4 AV 9 -40.0°F/-40.0°C to...
  • Page 19 Table 4: TEC2645-4 MS/TP Bus Objects (Part 2 of 4) Point Name Thermostat Point Range (Type/Address) BI 36 0 = Off Filter Alarm 1 = On BI 37 0 = Off Service Alarm 1 = On AV 39 40.0°F/4.5°C to...
  • Page 20 Table 4: TEC2645-4 MS/TP Bus Objects (Part 3 of 4) Point Name Thermostat Point Range (Type/Address) MSV 62 1 = 0 Hours Temporary Occupancy Time 2 = 1 Hour 3 = 2 Hours 4 = 3 Hours 5 = 4 Hours...
  • Page 21 Table 4: TEC2645-4 MS/TP Bus Objects (Part 4 of 4) Point Name Thermostat Point Range (Type/Address) 8, 9 Device 73aaa TEC2645-aaa Digital Outputs BV 70 to BV 77 N/A (Future Use) This MS/TP Bus object is readable and only writable if the corresponding override object is set. (For example, Room Temp has a corresponding override object of Room Temp Override.
  • Page 22: Tec26X7-4 And Tec26X7-4+Pir Series Thermostat Controllers

    TEC26x7-4 and TEC26x7-4+PIR Series Thermostat Controllers Table 5: TEC26x7-4 and TEC26x7-4+PIR Series MS/TP Bus Objects (Part 1 of 4) Point Name Thermostat Point Range (Type/Address) 1, 2 AV 7 -40.0°F/-40.0°C to Room Temp 122.0°F/50.0°F BV 8 0 = Normal Room Temp Override 1 = Override 3, 4 AV 9...
  • Page 23 Table 5: TEC26x7-4 and TEC26x7-4+PIR Series MS/TP Bus Objects (Part 2 of 4) Point Name Thermostat Point Range (Type/Address) 5, 6 BI 30 0 = Deactivated BI2 Status 1 = Activated BI 31 0 = Deactivated 5, 6 UI3 Status 1 = Activated BI 32 0 = Deactivated...
  • Page 24 Table 5: TEC26x7-4 and TEC26x7-4+PIR Series MS/TP Bus Objects (Part 3 of 4) Point Name Thermostat Point Range (Type/Address) MSV 54 1 = Not Used AUX (BO5) Configuration 2 = NO with Occ 3 = NC with Occ 6 = Network Controlled Password Value AV 56 0 to 1,000...
  • Page 25 Table 5: TEC26x7-4 and TEC26x7-4+PIR Series MS/TP Bus Objects (Part 4 of 4) Point Name Thermostat Point Range (Type/Address) Floating Motor Timing MSV 76 1 = 0.5 Minutes 2 = 1.0 Minute (TEC2627-4 Model) 3 = 1.5 Minutes 4 = 2.0 Minutes 5 = 2.5 Minutes 6 = 3.0 Minutes 7 = 3.5 Minutes...
  • Page 26: Tec2601-4 And Tec2601-4+Pir Thermostat Controllers

    TEC2601-4 and TEC2601-4+PIR Thermostat Controllers Table 6: TEC2601-4 and TEC2601-4+PIR MS/TP Bus Objects (Part 1 of 3) Point Name Thermostat Point Range (Type/Address) AV 7 -40.0°F/-40.0°C to Room Temp 122.0°F/50.0°C 2, 3 BV 8 0 = Normal Room Temp Override 1 = Override AV 9 -40.0°F/-40.0°C to...
  • Page 27 Table 6: TEC2601-4 and TEC2601-4+PIR MS/TP Bus Objects (Part 2 of 3) Point Name Thermostat Point Range (Type/Address) BI 40 0 = Off Fan Lock Alarm 1 = On AV 42 40.0°F/4.5°C to 2, 7 Occupied Heat Setpoint 90.0°F/32.0°C AV 43 54.0°F/12.0°C to 2, 7 Occupied Cool Setpoint...
  • Page 28 Table 6: TEC2601-4 and TEC2601-4+PIR MS/TP Bus Objects (Part 3 of 3) Point Name Thermostat Point Range (Type/Address) BV 62 0 = Off Fan Control 1 = On MV 63 1 = 0 Minutes Anticycle 2 = 1 Minute 3 = 2 Minutes 4 = 3 Minutes 5 = 4 Minutes 6 = 5 Minutes...
  • Page 29: Tec2602-4 And Tec2602-4+Pir Thermostat Controllers

    TEC2602-4 and TEC2602-4+PIR Thermostat Controllers Table 7: TEC2602-4 and TEC2602-4+PIR MS/TP Bus Objects (Part 1 of 4) Point Name Thermostat Point Range (Type/Address) AV 7 -40.0°F/-40.0°C to Room Temp 122.0°F/50.0°C 2, 3 BV 8 0 = Normal Room Temp Override 1 = Override AV 9 -40.0°F/-40.0°C to...
  • Page 30 Table 7: TEC2602-4 and TEC2602-4+PIR MS/TP Bus Objects (Part 2 of 4) Point Name Thermostat Point Range (Type/Address) BI 38 0 = Off Filter Alarm 1 = On BI 39 0 = Off Service Alarm 1 = On BI 40 0 = Off Fan Lock Alarm 1 = On...
  • Page 31 Table 7: TEC2602-4 and TEC2602-4+PIR MS/TP Bus Objects (Part 3 of 4) Point Name Thermostat Point Range (Type/Address) MV 61 1 = 0 Hours Temporary Occupancy Time 2 = 1 Hour 3 = 2 Hours 4 = 3 Hours 5 = 4 Hours 6 = 5 Hours 7 = 6 Hours 8 = 7 Hours...
  • Page 32 Table 7: TEC2602-4 and TEC2602-4+PIR MS/TP Bus Objects (Part 4 of 4) Point Name Thermostat Point Range (Type/Address) BV 86 0 = Off Compressor Interlock 1 = On TEC2602-4 to TEC2602-127 TEC2602-address Device 76aaa This MS/TP Bus object is readable and only writable if the corresponding override is set. (For example, Room Temp has a corresponding override object of Room Temp Override.
  • Page 33: Tec2603-4 And Tec2603-4+Pir Thermostat Controllers

    TEC2603-4 and TEC2603-4+PIR Thermostat Controllers Table 8: TEC2603-4 and TEC2603-4+PIR MS/TP Bus Objects (Part 1 of 4) Point Name Thermostat Point Range (Type/Address) AV 7 -40.0°F/-40.0°C to Room Temp 122.0°F/50.0°C 2, 3 BV 8 0 = Normal Room Temp Override 1 = Override AV 9 -40.0°F/-40.0°C to...
  • Page 34 Table 8: TEC2603-4 and TEC2603-4+PIR MS/TP Bus Objects (Part 2 of 4) Point Name Thermostat Point Range (Type/Address) BI 38 0 = Off Filter Alarm 1 = On BI 39 0 = Off Service Alarm 1 = On BI 40 0 = Off Fan Lock Alarm 1 = On...
  • Page 35 Table 8: TEC2603-4 and TEC2603-4+PIR MS/TP Bus Objects (Part 3 of 4) Point Name Thermostat Point Range (Type/Address) MV 61 1 = 0 Hours Temporary Occupancy Time 2 = 1 Hour 3 = 2 Hours 4 = 3 Hours 5 = 4 Hours 6 = 5 Hours 7 = 6 Hours 8 = 7 Hours...
  • Page 36 Table 8: TEC2603-4 and TEC2603-4+PIR MS/TP Bus Objects (Part 4 of 4) Point Name Thermostat Point Range (Type/Address) AV 68 0.5 Hours to Unoccupied Time 24.0 Hours MV 73 1 = One Stage Heating Stages 2 = Two Stages MV 74 1 = One Stage Cooling Stages 2 = Two Stages...
  • Page 37: Tec2613-4 And Tec2613-4+Pir Temperature And Humidity Controllers

    TEC2613-4 and TEC2613-4+PIR Temperature and Humidity Controllers Table 9: TEC2613-4 and TEC2613-4+PIR MS/TP Bus Objects (Part 1 of 4) Point Name Controller Point Range (Type/Address) AV 7 -40.0°F/-40.0°C to Room Temp 122.0°F/50.0°C BV 8 0 = Normal 2, 3 Room Temp Override 1 = Override AV 9 -40.0°F/-40.0°C to...
  • Page 38 Table 9: TEC2613-4 and TEC2613-4+PIR MS/TP Bus Objects (Part 2 of 4) Point Name Controller Point Range (Type/Address) BI 38 0 = Off Filter Alarm 1 = On BI 39 0 = Off Service Alarm 1 = On BI 40 0 = Off Fan Lock Alarm 1 = On...
  • Page 39 Table 9: TEC2613-4 and TEC2613-4+PIR MS/TP Bus Objects (Part 3 of 4) Point Name Controller Point Range (Type/Address) MV 61 1 = 0 Hours Temporary Occupancy Time 2 = 1 Hour 3 = 2 Hours 4 = 3 Hours 5 = 4 Hours 6 = 5 Hours 7 = 6 Hours 8 = 7 Hours...
  • Page 40 Table 9: TEC2613-4 and TEC2613-4+PIR MS/TP Bus Objects (Part 4 of 4) Point Name Controller Point Range (Type/Address) Eff Reset Humidification AV 96 0 to 100% RH Spt AV 97 50 to 90% Humidification High Limit Spt AV 98 10 to 90% Low RH Setpoint AV 99 -40.0°F/-40.0°C to...
  • Page 41: Tec2604-4 And Tec2604-4+Pir Thermostat Controllers

    TEC2604-4 and TEC2604-4+PIR Thermostat Controllers Table 10: TEC2604-4 and TEC2604-4+PIR MS/TP Bus Objects (Part 1 of 4) Point Name Thermostat Point Range (Type/Address) AV 7 -40.0°F/-40.0°C to Room Temp 122.0°F/50.0°C 2, 3 BV 8 0 = Normal Room Temp Override 1 = Override AV 9 -40.0°F/-40.0°C to...
  • Page 42 Table 10: TEC2604-4 and TEC2604-4+PIR MS/TP Bus Objects (Part 2 of 4) Point Name Thermostat Point Range (Type/Address) BI 38 0 = Off Filter Alarm 1 = On BI 39 0 = Off Service Alarm 1 = On BI 40 0 = Off Fan Lock Alarm 1 = On...
  • Page 43 Table 10: TEC2604-4 and TEC2604-4+PIR MS/TP Bus Objects (Part 3 of 4) Point Name Thermostat Point Range (Type/Address) MV 61 1 = 0 Hours Temporary Occupancy Time 2 = 1 Hour 3 = 2 Hours 4 = 3 Hours 5 = 4 Hours 6 = 5 Hours 7 = 6 Hours 8 = 7 Hours...
  • Page 44: Tec262Xx-0+Pir Thermostat Controllers

    Table 10: TEC2604-4 and TEC2604-4+PIR MS/TP Bus Objects (Part 4 of 4) Point Name Thermostat Point Range (Type/Address) AV 80 50.0°F/10.0°C to Mixed Air Setpoint 90.0°F/32.0°C TEC2604-4 to TEC2604-127 TEC2604-address Device 76aaa This MS/TP Bus object is readable and only writable if the corresponding override is set. (For example, Room Temp has a corresponding override object of Room Temp Override.
  • Page 45 Table 11: TEC26xx-0+PIR (Part 2 of 5) Point Name Thermostat Point Range (Type/Address) Fan Mode MSV 17 Available state text and default value depends on Fan Mode Sequence (MV58) value upon device discovery. MSV17 Index function - MSV58 Text Index: 1 = 1 Low - 2 Medium - 3 High 2 = 1 Low - 2 High 3 = 1 Low - 2 Medium - 3 High - 4 Auto...
  • Page 46 Table 11: TEC26xx-0+PIR (Part 3 of 5) Point Name Thermostat Point Range (Type/Address) Unoccupied Cool Setpoint AV 44 54.0°F/12.0°C to 100.0°F/37.5°C BI 1 Configuration MSV 46 1 = None 2 = Rem NSB 3 = Motion N.O. 4 = Motion N.C. 5 = Window BI 2 Configuration MSV 47...
  • Page 47 Table 11: TEC26xx-0+PIR (Part 4 of 5) Point Name Thermostat Point Range (Type/Address) Temporary Occupancy Time MSV 62 1 = 0 Hour 2 = 1 Hour 3 = 2 Hours 4 = 3 Hours 5 = 4 Hours 6 = 5 Hours 7 = 6 Hours 8 = 7 Hours 9 = 8 Hours...
  • Page 48 507 E. Michigan Street, Milwaukee, WI 53202 Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc. All other marks herein are the marks of their respective owners. © 2013 Johnson Controls, Inc. TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin Published in U.S.A.