Table Of Contents Thank you for purchasing the ELiS curtain. This operation manual has been issued by the FLOWAIR GŁOGOWSKI 1. GENERAL INFORMATION ............3 I BRZEZIŃSKI SP.J. company. The manufacturer reserves the 2. TECHNICAL DATA ..............3 right to make revisions and changes in the operation manual at 2.1.
ELIS A-E-150 – curtain with electrical heat exchanger max. ELIS types: range 3 m; ELIS A-W-200 – curtain with water heat exchanger max. range ELIS A-W-100 – curtain with water heat exchanger max. range 3 m; 3 m; ELIS A-N-200 – curtain without heat exchanger (ambient);...
, at the distance of 3 m apart of the unit. 2.4. AIR VOLUME step A-W-100; A-N-100; A-E-100 A-W-150; A-N-150; A-E-150 A-W-200; A-N-200; A-E-200 1500m 2500 m 3500 m 1150m 2100 m 2900 m 800m 1650 m 2400 m www.flowair.com |4...
29/28/27 V – air flow Tw1 – inlet water temperature PT – heating capacity Tw2 – outlet water temperature Tp1 – inlet air temperature Qw – heating water stream Tp2 – outlet air temperature Δpw – water pressure www.flowair.com |6...
(like is shown below), all electrical conntection should be done before installing following curtain. 4.1. RECOMMENDATION OF MONTAGE DISTANCES 4.2. MOUNTING BY RODS UNDER THE CEILING While mounting curtains under the ceiling, 4 rods M8 should be screwed minimum 20 mm deep. www.flowair.com |7...
Brackets ELiS A 2 x bracket ELiS A 4 x plug (Ø10)* 4 x double threaded screw (M8)* 4 x washer (M8)* 4 x nut (M8)* 4 x allen screw (M8) * not included www.flowair.com |8...
200 – 240V 50/60Hz 200 – 240V 50/60Hz Max water temperature: +93 Max water temperature: Max water pressure : 2,1MPa Max water pressure Kvs: 3,4 m : 2,1MPa Opening time: 18 s Kvs: 3,0 m Opening time: 18 s www.flowair.com |10...
*K1 programme – Signal from door switch or thermostat is MASTER-SLAVE connectors; main signal for the device to run PT-1000 connectors; **K2 programme – Signal from door switch is main signal for the device to run and thermostat is in charge of valve/heaters www.flowair.com |11...
Door contact DCe/DCm (door closed – contacts opened; door opened – contacts closed) ATTENTION: Switch 4 on SW3 to the position “E” and then restart the system switching it off for 5 seconds. Each time the device is switched off the heaters are being cooled for next 15 seconds www.flowair.com |12...
Door contact DCe/DCm (door closed – contacts opened; door opened – contacts closed) ATTENTION: Switch 4 on SW3 to the position “E” and then restart the system switching it off for 5 seconds. Each time the device is switched off the heaters are being cooled for next 15 seconds. www.flowair.com |13...
Dla ostatniego urządzenia pracującego w sieci BMS wymagane jest ustawienie przełącznika SW2 w prawą pozycję. UWAGA: 5.3.7. CONTROL SYSTEM – SETTING BMS ADDRESS There is a possibility to set 31 addresses which are set binary on SW1 switch: Address Switch down Switch up www.flowair.com |14...
2nd step of fan is on FAN_SPEED3 3rd step of fan is on Current Valve status VALVE_CLOSE Valve closing 0x05 CurtainValveState VALVE_OPEN Valve opening Set value for door contact DOOR_CLOSE Door is closed 0x08 ContactDoor DOOR_OPEN Door is open www.flowair.com |15...