Page 1
Wireless Access INSTALLATION INSTRUCTIONS WIRELESS READER INTERFACE - OUTDOOR (WRI-OTD-12VDC or AUWRI-OTD-12VDC) The most current version of this document is available for download at: http://www.ir-swa.com P/N: M053-003-C...
Wireless Access System. AUWRI-OTD-12VDC is an Australian version of the outdoor wireless reader interface. In this manual, WRI-OTD refers to either a WRI-OTD-12VDC or an AUWRI-OTD-12VDC model. After completing this installation refer to the “Configuring and Operating the Schlage Wireless Access System” manual. Table of Contents Schlage Wireless Access System Components....................4...
Wireless Access 1. Schlage Wireless Access System Components 1.1 Overview Every access control system that uses Schlage Wireless Access contains two different types of modules (Figure 1-1): • at least one Wireless Panel Interface Module (WPIM), and • at least one Wireless Access Point Module (WAPM) Figure 1-1 –...
Wireless Access • Pencil (#2 lead) • Mounting hardware (not provided), four ¼” diameter screws or bolts and/or anchors, type and length of fasteners depend on the mounting surface. 2.2 Remote Antenna If the WRI-OTD installation uses the Remote Antenna Module (RAM) option, please refer to the “Remote Antenna Module Installation”...
Page 7
Wireless Access Figure 2-1 – Outdoor Gate Installation WPIM location guidelines for outdoor gate applications: • Mount the WPIM indoors, within the secured portion of the premises. • Install the WPIM just inside the building’s outer wall that faces the gate. •...
Page 8
Wireless Access This section describes the ideal locations to mount the WRI-OTD and WPIM to control a typical cabled hoist elevator (Figure 2-2) or a typical hydraulic elevator (Figure 2-3). Figure 2-2 – Cabled Hoist Elevator Installation Figure 2-3 – Hydraulic Elevator Installation 2.3.2.1 Cabled hoist machine installations with upper machine rooms (Figure 2-2) Mount the WPIM inside the secured portion of the premises.
Wireless Access 2.3.3 Indoor WRI-OTD Reader & Electrified Lock/Access Point Applications These applications include door installations with magnetic locks, electric strikes, electrified exit devices (using EL kits), or automatic door openers; Wiegand or clock & data type readers; and other peripheral hardware.
Wireless Access 2.5 Getting Wires In & Out of the WRI-OTD 2.5.1 Weather Tight Installation A NEMA 4X certified Wiring Gland (Figure 2-5) should be used to achieve a weather tight installation when wires enter or exit the WRI-OTD. Wiring Glands are available from Bud Industries, Inc.
Page 11
Wireless Access Figure 2-6 – WRI-OTD Printed Circuit Board (PCB) Ingersoll Rand Security Technologies 245 W. Roosevelt Road, Bldg 7, Suite 48, West Chicago, IL 60185 / (800) 313-2962 / (630) 293-4257 fax P/N: M053-003-C www.ir-swa.com Page 11 of 20...
Page 12
Wireless Access Figure 2-7 – Typical Access Point Configuration 2.6.1 DC Input Power The DC Input Power connection is mandatory. An external, UL approved, DC power supply that can supply 12 VDC (7-14VDC range) must be provided. The DC power supply must be capable of providing 300 mA of current to power the WRI-OTD.
Page 13
Wireless Access control peripherals connected to the WRI-OTD to the 300 mA to determine the overall size of the DC power supply. Connector J3 (Figure 2-6) is where the DC power is connected to the WRI-OTD PCB. Table 2-1 shows how to connect the DC power. Make certain to observe the polarity. Connect the shield of the DC Input Power cable to the Ground (-) terminal at the power supply.
Page 14
Wireless Access REQUEST R_ENTER J7-1 A dry contact closure across these terminals initiates a request to enter. J7-2 ENTER REQUEST R_EXIT J7-3 A dry contact closure across these terminals initiates a request to exit. J7-4 EXIT DOOR A dry contact closure across these terminals indicates to the J7-5 POSITION ACP that the access point portal is closed.
Page 15
Wireless Access Figure 2-8 – Portal Output Suppression Diagram 2.6.6 Card Readers Any input device with a Wiegand or Clock & Data bit stream can be used with the WRI-OTD. A transaction must be a single bit stream of between 4 and 255 bits. The WRI-OTD provides two Card Reader interfaces.
Page 16
Wireless Access CLK/D1 J4-1 Card Reader inputs, each input line has a 3.3k pull up resistor to 5V, and a 12V transient suppressor to GND. DATA/D0 J4-2 Reader power supply output. The WRI-OTD PC board routes 12VDC+ J4-3 its own power supply input to these terminals, so the readers see the same supply as the WRI-OTD.
“PIM Installation Instruction” manual. If the WPIM is installed, then you are ready to link and configure your Schlage Wireless Access System, please refer to the “Configuring & Operating a Schlage Wireless Access System”...
• Do not co-locate and operate in conjunction with any other antenna or transmitter. • Changes or modifications not expressly approved by Schlage could void the users authority to operate the equipment. Ingersoll Rand Security Technologies 245 W. Roosevelt Road, Bldg 7, Suite 48, West Chicago, IL 60185 / (800) 313-2962 / (630) 293-4257 fax P/N: M053-003-C www.ir-swa.com...