KFP-CE4 Series
Operation Manual
P/N 501-415503-2-31 • REV 03.10 • ISS 08NOV13

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the KFP-CE4 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Kilsen KFP-CE4

  • Page 1 KFP-CE4 Series Operation Manual P/N 501-415503-2-31 • REV 03.10 • ISS 08NOV13...
  • Page 2 Copyright © 2013 UTC Fire & Security. All rights reserved. Trademarks and The KFP-CE4 Series name and logo are trademarks of patents UTC Fire & Security. Other trade names used in this document may be trademarks or registered trademarks of the manufacturers or vendors of the respective products.
  • Page 3: Table Of Contents

    Audible indicators 6 Summary of status indications 6 Sounder activation during a fire alarm 9 Control panel operation 10 User levels 10 Public user level operation 10 Operator user level operation 12 Maintenance 17 Regulatory information 18 KFP-CE4 Series Operation Manual...
  • Page 4: Important Information

    Installation in accordance with this manual, applicable codes, and the instructions of the authority having jurisdiction is mandatory. While every precaution has been taken during the preparation of this manual to ensure the accuracy of its contents, UTCFS assumes no responsibility for errors or omissions. KFP-CE4 Series Operation Manual...
  • Page 5: Introduction

    Introduction This is the operation manual for KFP-CE4 Series conventional fire alarm and evacuation control panels. Read these instructions and all related documentation entirely before operating this product. Product range The KFP-CE4 Series includes the models shown below. Table 1: KFP-CE4 Series models...
  • Page 6: Control Panel Overview

    19. Earth Fault LED 9. Reserved for special use 20. Supply Fault LED 10. Expansion I/O Fault/Disabled LED 21. Fire Routing Delay button and LED 11. General Disable button and LED 22. Fire Routing Start button and LEDs KFP-CE4 Series Operation Manual...
  • Page 7: Operator Controls And Indicators

    LED indicates that the evacuation area is disabled or is being tested. Supply LED Green Indicates that the system is powered up correctly. General Fault LED Yellow Indicates a fault. The corresponding zone, device, or function fault LED also flashes. KFP-CE4 Series Operation Manual...
  • Page 8 Tests a zone, evacuation area or fire routing and LED (when pressed with the corresponding button). A steady General Test LED and a steady yellow LED for the corresponding zone, evacuation area, or fire routing indicates a test. KFP-CE4 Series Operation Manual...
  • Page 9 A steady LED indicates that a fire routing delay is configured and enabled. A flashing LED indicates that a fire routing delay is counting (fire routing will be activated when the configured delay elapses). KFP-CE4 Series Operation Manual...
  • Page 10: Audible Indicators

    Shows which zones are in alarm. • Evacuation Area LED: On steady to indicate that sounders are active in those areas (sounding). • All Sounders Start LED is steady (if all evacuation areas are active). KFP-CE4 Series Operation Manual...
  • Page 11 • General Fault LED: Flashing. • Supply Fault LED: Flashing. • Control panel buzzer: Sounding intermittent. Earth fault indication: • General Fault LED: Flashing. • Earth Fault LED: On steady. • Control panel buzzer: Sounding intermittent. KFP-CE4 Series Operation Manual...
  • Page 12 An evacuation area test is indicated as follows: • General Test LED: On steady. • Evacuation Area: On steady yellow. • Control panel buzzer: Off. A fire routing test is indicated as follows: • General Test LED: On steady. KFP-CE4 Series Operation Manual...
  • Page 13: Sounder Activation During A Fire Alarm

    1 or zone 2. Sounders in evacuation area 2 are activated by a fire alarm in zone 3 or zone 4. NEN 2575 with one All sounders are activated simultaneously by a fire alarm in any evacuation area zone KFP-CE4 Series Operation Manual...
  • Page 14: Control Panel Operation

    Acknowledge a system event and silence the control panel buzzer • Activate an evacuation alarm • Cancel an active fire routing delay • Perform a control panel LED and buzzer test • Display local indications only (for control panels with repeater functionality) KFP-CE4 Series Operation Manual...
  • Page 15 For control panels connected in an evacuation panel network with repeater functionality, an indication is activated if any control panel in the network being repeated has the feature activated. For zone indications which are global in the KFP-CE4 Series Operation Manual...
  • Page 16: Operator User Level Operation

    Those tasks included in the topic “Public user level operation” on page 10 are also available at the operator user level. This user level lets you: • Reset the control panel • Stop or restart sounders KFP-CE4 Series Operation Manual...
  • Page 17 (by pressing the All Sounders Stop button) and remain stopped when the standard fire routing delay time has elapsed. The extended fire routing delay also becomes the active delay when an extended fire routing delay switch is activated while the standard fire routing delay elapses. KFP-CE4 Series Operation Manual...
  • Page 18 No fire alarm or faults are indicated for disabled zones. Testing evacuation sounders To test evacuation sounders, press the General Test button, and then press the Evacuation Area button. Evacuation sounders can only be tested when the control panel is in standby state. KFP-CE4 Series Operation Manual...
  • Page 19 To end the test, press the General Test button, and then press the Fire Routing Start button again. If there is a fire alarm the fire panel will exit the test and respond to the alarm as configured. KFP-CE4 Series Operation Manual...
  • Page 20 To enable a disabled option, press the General Disable button for more than 3 seconds, press the 1 and 3 buttons to select the option to be enabled, and then press Enter. Note: Disabled expansion boards do not operate or indicate faults. KFP-CE4 Series Operation Manual...
  • Page 21: Maintenance

    Keep the outside and inside of the control panel clean. Carry out periodic cleaning using a damp cloth for the outside. Do not use products containing solvents to clean the unit. Do not clean the inside of the cabinet with liquid products. KFP-CE4 Series Operation Manual...
  • Page 22: Regulatory Information

    Regulatory information European standards for fire control and indicating equipment The KFP-CE4 Series four-zone conventional fire and evacuation control panels have been designed in accordance with European EN 54-2, EN 54-4 and NEN 2575 standards. In addition, the control panel complies with the following EN 54-2 optional...
  • Page 23 UTC Fire & Security B.V., Kelvinstraat 7,6003 DH Weert, The Netherlands Year of first CE marking Declaration of Performance 360-3100-1699 number Product identification See model number on product identification label Intended use See DoP point 3 Essential characteristics See DoP point 9 KFP-CE4 Series Operation Manual...