Setting Fan Speed
Heat Fan Speed Switches 1 & 2
OFF
ON
OFF
ON
OFF/OFF
Heating
CFM
1300
Cooling
CFM
1640
Heating
CFM
760
Cooling
CFM
980
Cool Fan Speed Switches 5 & 6
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Note: Power to the Viessmann AirflowPLUS air handler must be turned off before changing switch settings.
The above values are approximations only, actual results may vary.
Note: Factory switch set positions are shown in bold.
(continued)
OFF
1300
980
OFF
ON
675
ON
760
Adjust Fan Speed Switches 3 & 4
ON/OFF
1430
1804
830
1050
OFF
1640
OFF
1270
ON
980
ON
740
Cool Fan Speed Profiles Switches 7 & 8
Pre Run
Motor %
Time Min.
5
82
3
82
2
82
-
AH2A-354 Viessmann AirflowPLUS Air Handler
1/2 hp ECM - Air Flow Selectable Options
Set at dip switch S2.
OFF/ON
OFF/OFF
1140
980
1440
1270
660
760
860
740
Short Run
Time Min.
2
2
-
-
-
ON/OFF
1050
1400
830
800
Motor %
Motor OFF
Time Min.
88
2
88
2
-
4
-
4
Installation
OFF/ON
860
1100
660
650
Motor %
75
75
75
75
33