APRICUS TEMPERMATE OWNERS AND INSTALLATION MANUAL Note: This manual must be left with a responsible person after installation and remain on site.
6 years. Make sure you use a licensed person to install this water heater and ask for your Compliance Certificate. Notification of Apricus Tempermate Warm Water Installation The following Apricus Warm Water System(s) and UV Sterilisation System(s) have been installed. Warm Water System: ...
Contents IMPORTANT ..........................3 GENERAL ............................. 6 BENEFITS OF WARM WATER SYSTEMS ....................6 SAFETY ..............................6 TECHNICAL DATA ......................... 7 WARM WATER COMPONENTS ......................8 DIMENSIONS ............................9 OPERATION ..........................10 HYDRAULIC CHARACTERISTICS......................11 SYSTEM SIZING ..........................12 INSTALLATION ........................... 13 INSTALLATION STANDARDS ......................
Page 5
UV DISINFECTION ........................31 UV SYSTEM BYPASS LINE ........................31 OPTIONAL COMPONENTS FOR UV ....................32 MAINTENANCE CHECK LOG ......................33 WATER QUALITY TEST LOG ......................34 COMMISSIONING REPORT ......................35 SERVICE REPORT ........................39 WARM WATER UNIT WARRANTY ....................43...
The Apricus Tempermate Warm Water System provides water at a safe and usable temperature in a situation where the control of the temperature of the water discharging from an outlet is of the utmost Importance i.e.
TECHNICAL DATA Temperature adjustment range: 30 – 50°C Factory pre-set temperature: 41°C Set temperature: must be commissioned on site to achieve desired temperature Temperature control: ±2°C Cold inlet temperature supply (min – max): 5°C – 30°C Hot inlet temperature supply (min – max): 55°C –...
OPERATION The Apricus Tempermate warm water system is a centralised warm water plant which allows warm water to be circulated around a building. The system utilises a thermostatic mixing valve(s) which mixes hot and cold water in such a way as to maintain the set temperature of the mixed water at the outlet.
The system must be sized taking into account the current legislation with regard to the nominal flow rate of each outlet. The reference is AS/NZS 3500.1. Note that the Apricus Tempermate systems should be sized on maximum nominal flows. Pipe dimensions are based on velocities of 1.5m/s and the valves not exceeding the recommended maximum differential pressure of 150kPa.
= 750 x 20% diversified flow = 150 l/min SELECT APRICUS TEMPERMATE ‘AT240’ WITH MAX NOMINAL FLOW OF 180L/M Please note that the above calculation is a quick sizing guide only. Flow rates and loading units to work out actual diversified flow are dependent on the type of application, ie hotel, apartments, commercial premises, aged care facility etc, and should be calculated by an experienced designer or engineer.
AS/NZS 3500.4 and all local codes and regulatory authority requirements. SYSTEM PARAMETERS Prior to the installation of the Apricus Tempermate, the system must be checked to ensure that the system operating conditions fall within the recommended operating range of the unit, i.e. verify supply temperatures, supply pressures, risk assessments, etc.
To ensure that the performance of the Apricus Tempermate is maintained (in the event of cold water failure), the temperature of the hot water supply at the point of entry to the unit must be a minimum of 10°C higher than the set mixed water discharge temperature.
PLUMBING CONNECTIONS Check the connections between the Warm Water System and hot water plant closely for correct connection using the plumbing diagrams provided. The following points are of particular importance: 1. A non-return valve must be installed with the Warm Water System between the cold water take off to the Warm Water System and the inlet to the water heating plant.
COMMISSIONING THE TMV Upon completion of the installation, the valve should be tested and commissioned in accordance with AS 4032.3 as per the procedure outlined below or as specified by the local authority. Use the “Commissioning Report” form at the back of this manual. The following instructions should be read and understood prior to commissioning the Caleffi 2522TM series valve.
f) Perform the thermal shut-off test. Isolate the cold water supply to the Caleffi valve and monitor the mixed water temperature. The outlet flow should quickly cease flowing. TIP: to perform the thermal shut off test on each TMV individually without interrupting the warm water supply to the system;...
3. Monitor the return temperature on the digital thermometer inserted in the cold water inlet connection of the Warm Water temperature. Note: During recirculation i.e. when water is not being drawn, the Apricus Tempermate Warm Water System requires a flow rate of at least 4 litres per minute per valve and a temperature differential between the outlet and return of at least 3°C to maintain the...
MAINTENANCE AND WATER TESTING REQUIREMENTS The following table details legislative requirements for the maintenance and water testing of warm water systems by State, as at December 2014. State Mandatory Inspections & Maintenance Mandatory Microbial Water Testing TMV's to be cleaned and maintained annually (1) Not required TMV's to be cleaned and maintained annually (1) Not required...
In-service tests should be carried out regularly to monitor and record the performance of the Apricus Tempermate in accordance with AS 4032.3. Deterioration in performance can indicate the need for servicing of the valves and/or water supply. If, during these tests, the mixed water temperature has changed significantly from the previous test results, record the change before re- adjusting the mixed water temperature.
5 YEAR SERVICE The thermostat and o-rings must be replaced every 5 years, as required by AS4032.3. The designed minimum service life of these components is 5 years providing the valve is operated within the recommended operating parameters. However when conditions or usage do not conform to the recommended operating parameters or conditions, the thermostat and o-rings may need to be replaced more frequently.
SPARE PARTS With reference to the exploded diagram, the following spare parts are available on request for Caleffi 2522TM series valves: Kit A - Service Kit for the inlet sub-assembly. Kit B - Service Kit for the internal components. ...
MICROBIAL WATER TESTING Regular maintenance, inspection and cleaning programs are the key to reducing the risk of Legionella transmission. The microbiological monitoring of warm water systems for Legionella should never be used to replace these practices, but may be used in conjunction with them to validate their effectiveness.
LEGIONELLA TESTING Unless prescribed otherwise by a regulating authority, sampling at the following rates are recommended: STATE WATER SAMPLING FREQUENCY Take water samples from 2 Monthly for first 12 months, then Victoria fixtures every 3 months (see notes) Take water samples from 2 Monthly for first 3 months, then every fixtures 6 months (see notes)
Page 27
to have appropriate monitoring programs in place which satisfy Section 19 of the NSW Code of Practice for the Control of Legionnaires’ Disease. Note: The above is the minimum requirement for all warm water systems in NSW. Some NSW Health Care facilities may require additional testing as determined by the institutions management after conducting a risk assessment and;...
LEGIONELLA DETECTION Legionella Count Action A count of less than 10cfu/ml is considered satisfactory. No additional action is required other than continuing existing maintenance and testing procedures. < 10 cfu/ml Note: Less than 10cfu/ml is considered as “not detected” for the purposes of State legislation and this procedure.
THERMAL DISINFECTION If decontamination of the warm water system is required following detection of Legionella in a water sample, the entire warm water system including all pipes and fittings including TMVs, taps and shower heads must be sanitised by heat. Note: alternatives such as chlorination, chlorine dioxide, ozone and other chemical options may be used for disinfection but are not detailed in this procedure.
Page 30
5. Open each outlet connected to the warm water system starting with the most distant point and flush each outlet line for 5 minutes 6. Record the temperature and duration of the sanitation period. Note: the total sanitation period from when the warm water system reaches the sanitation temperature must be at least one (1) hour.
UV DISINFECTION The Apricus Tempermate can be to be supplied complete with UV disinfection. UV disinfection is an efficient, low cost and environmentally friendly process. UV light kills pathogenic micro-organisms quickly without leaving any residues, harmful by-products or affecting the smell or taste of the water.
OPTIONAL COMPONENTS FOR UV AUTOMATIC TEMPERATURE SHUT OFF A solenoid shutoff control valve may be installed prior to the UV system to automatically shut off the supply of water if the warm water outlet reaches 60°C. Once the system reaches this temperature limit, switch will activate the solenoid shutoff valve which will stop the supply of warm water.
MAINTENANCE CHECK LOG TMV 1 TMV 2 TMV 3 TMV 4 Return Closest Shut off Test test test test test test UV lamp Date outlet Comments Checked By point point point point point cleaned temp hours temp temp temp temp temp Final...
Job No COMMISSIONING REPORT FOR APRICUS TEMPERMATE WARM WATER UNIT Location Name of Establishment:…………………………………………………………………………... Address of Establishment:………………………………………………………………………… Contact Person:…………………...Tel:………………………….Date:…………………………. Work order No:……………………………………………………………………………………... Installation conditions Make and Model of hot water unit:……………………………………………………………….. Temp of Hot Water…………………………..°C, Pressure…………..………………………kPa Cold water supply via…………………………………, Pressure reducing valve fitted: YES/NO Temperature of Cold Water…………………...
Page 36
Valve installed to requirements of: a) The drawing and specification YES/NO b) The valve manufacturer/supplier YES/NO c) The HOSPLAN code for TMV YES/NO d) The local water supply authority YES/NO If NO, give details and action taken……………………………………………………………… ……………………………………………………………………………………………………..……………………………………………………………………………………………………..Test Results (complete the attached table) Valve considered satisfactory for use: YES/NO If NO, state reason and action taken………………………………………………………………...
Page 37
NOTE A duplicate copy of this report is to be retained at the site for any inspection by authorised persons e.g. Department of Health The following information is to be provided by site manager/owner: Valve size and installation recommended by (Name):………………………………………….. Valve supplied by (Name):…………………………………………………………………….…...
Page 38
Test Point Temperature Flow rate @ full flow @ min flow TMV 1 TMV 2 TMV 3 TMV 4 Warm Water *Name/Type/Size Flow rate of Design Warm Temp. of Warm Water (°C) Outlet Fixture Water (l/sec) & Location of Outlet Fixture **All req’d **All req’d One Outlet in...
Job No SERVICE REPORT FOR APRICUS TEMPERMATE WARM WATER UNIT Location Name of Establishment:…………………………………………………………………………..Address of Establishment:………………………………………………………………………….. Contact Person:…………………...Tel:………………………….Date:…………………………..Work order No:…………………………………………………………………………………..… Installation conditions Make and Model of hot water unit:………………………………………………………………..Make of mixing valve; Caleffi Model No 252225TM Size 25MM Valve Location/building:…………………………………………………………………………..
Page 40
Valve installed to requirements of: e) The drawing and specification YES/NO f) The valve manufacturer/supplier YES/NO g) The HOSPLAN code for TMV YES/NO h) The local water supply authority YES/NO If NO, give details and action taken………………………………………………...……………… …………………………………………………………………………………………..…………. ………………………………………………………………………………………………..……. Any current complaints concerning installation or operation reported by establishment personnel or stated in previous report: If YES, give details…………………………………………………………………….....…….
Page 41
It is hereby certified that all service work has been carried out by the undersigned in accordance with the requirements of the HOSPLAN Code of Practice for thermostatic mixing valves. Name of Licensed Plumber (Print):…………………………………………………….....…. Signature:………………………………………….. Licence/Certificate No:…………....….. Business Name of Plumbing Contractor:………………………………………………......Contractor’s Authority No:………………………………...
(iv) The cost of delivery or transportation of the product. (v) Normal wear and tear and reasonable abrasion. (vi) If the product has been modified or repaired by anyone other than a warranty service by Apricus Australia or if it is repaired using unauthorised spare parts (vii) The cost of new installation or complete removal of the product.