Troubleshooting
To avoid risk of electrical shock, personal injury, or death, disconnect electrical power source to unit, unless test
procedures require power to be connected. Discharge capacitor through a resistor before attempting to service.
Ensure all ground wires are connected before certifying unit as repaired and/or operational.
VCC3 Inverter Diagnostic Codes
Code
Compressor
Status
1 Flash
ON
(every 15
seconds)
OFF
2 Flashes
OFF
(every 5 sec-
onds)
3 Flashes
OFF
(every 5 sec-
onds)
4 Flashes
OFF
(every 5 sec-
onds)
No Flash
OFF
40
!
WARNING
Possible Fault
1. No failure
• If system is not working properly, check other refrigeration
detected
components.
1. No signal
• If refrigerator settings (thermistor conditions) are at levels
from control
in which the compressor should be "ON".
board
• Unplug inverter from power supply and wait for 2
2. Open
minutes, reconnect the inverter to the power supply
Thermistor
and wait for 12 minutes.
• If inverter still shows 1 flash code and compressor is
OFF, then check the control board.
1. No signal
• Check frequency cable connection
from the con-
• If frequency cable connection is good , replace
trol board
inverter.
1. Compressor
• Check compressor/inverter cable connection
/ inverter cable
• Check compressor winding resistances (among the 3
open circuit
terminal hermetic pins)
2. Compressor
• If resistances are within specifications and
winding open
compressor/inverter cable is OK, replace inverter.
circuit
1. Compressor
• Check compressor input power
damaged /
• Check compressor winding resistances
system
• Check leakage current between hermetic terminal
damaged
pins and compressor shell.
• If resistance or leakage current is out of spec, replace
the compressor.
• If resistance and leakage current are within spec,
check inverter/compressor cable for open circuit.
• Unplug inverter from power supply and wait for 2
minutes, reconnect the inverter to the power supply
and wait for 12 minutes.
• If inverter still shows 4 flash code and compressor is
OFF, replace the compressor.
1. No input
• Check the input power (115V)
power
• If there is no signal, check input power connections
2. Inverter
• If voltage is within specs, unplug inverter from power
damaged
supply and wait for 2 minutes, reconnect the inverter to
the power supply and wait for 12 minutes.
• If inverter still shows no flash code and compressor is
OFF, change the inverter.
• If the inverter shows no flash code and the compressor is
ON, diagnostic function is not working properly.
Service Action