6.7 Side Venting Terminal Requirements of
• USA - National Fuel Gas Code, ANSI 223.1/NFPA 54.
• Canada - Natural Gas and Propane Installation Code, CAN/CSA B149.1
Venting terminal from doors and windows
Venting terminal from forced air inlet of other appliances
Venting terminal from snow level
Venting terminal from vegetation
Venting terminal from public walkway
FIGURE 6-12
FIGURE 6-13
Forced Air
Inlet
FIGURE 6-14
3' (0.9m)
Minimum
6 - COMBUSTION AIR AND VENT PIPING
Termination must be
12" (305mm) from
or below doors,
windows or gravity
inlet.
Termination
12"
(305mm)
Minimum
Termination
3' (0.9m)
[If located
within 10' (3m)
of forced air
Less than
inlet]
10' (3m)
Minimum
:
Doors &
Windows
Condensate
Forced Air
Inlet
Grade, Snow
& Ice
"L"
Corner
28
See fi gure 6-12
See fi gure 6-13
See fi gure 6-14
See fi gure 6-15
See fi gure 6-16
Combustion air and vent termination
must be 12" (305mm) from or below
doors, windows or gravity inlet.
Vent gas may condense, forming
moisture, may be corrosive. Protect
building materials at vent from exhaust
of vent gas.
Terminate venting system 3' (0.9m)
above and 10' (3.0m) from any forced
air inlet (except boiler's combustion
air inlet).
Terminate vent system bottom,
minimum 12" (300 mm) above highest
anticipated snow level.
Avoid locations where snow may drift
and block vent and combustion air. Ice
or snow may cause boiler to shut down
if vent or combustion air becomes
obstructed.
Vent termination shall NOT be installed
closer than 3' (0.9m) from inside
corner of "L" shaped structure.