Daikin HXHD125A7V1B Installation Manual page 25

Hxhd125 series
Table of Contents

Advertisement

Possible types of benefit kWh rate power supply
Possible connections and requirements to connect the equipment to
such power supply are illustrated in the figures below (also refer to
"9.8. Field setting table" on page
[6-04]=1
1
L N
1
2
S1S
3
L N
2
1
S1S
2
3
L N
3
1
S1S
2
3
6
L N
X1M
7 8
1 Benefit kWh rate power supply box
2 Receiver controlling the signal of the electricity company
3 Benefit kWh rate power supply
4 Voltage free contact to indoor unit
5 Normal kWh rate power supply
6 Fuse (field supply)
NOTICE
In case of benefit kWh rate power supply installation,
remove the wiring bridges on X2M before installing the
normal kWh rate power supply.
HXHD125A7V1B
VRVIII system indoor unit
4PW62584-1A – 11.2010
38):
[6-04]=2
1
L N
1
2
S1S
4
3
L N
2
1
S1S
2
4
3
L N
3
1
S1S
2
4
3
L N
4
5
X3M
8 9
X2M
8 9
10 11
X2M
Type 1
The benefit kWh rate power supply is of the type that power supply is
not interrupted.
Type 2
The benefit kWh rate power supply is of the type that power supply
will be interrupted after elapse of time.
Type 3
The benefit kWh rate power supply is of the type that power supply is
interrupted immediately.
When parameter [6-04]=1 at the moment that the benefit kWh rate
4
signal is sent by the electricity company, that contact will open and
the unit will go in forced off mode
When parameter [6-04]=2 at the moment that the benefit kWh rate
signal is sent by the electricity company, that contact will close and
the unit will go in forced off mode
4
4
(1) When the signal is released again, the voltage free contact will close and
the unit will restart operation. It is therefore important to leave the auto
restart function enabled. Refer to field setting
page 29
in the chapter
(2) When the signal is released again, the voltage free contact will open and
the unit will restart operation. It is therefore important to leave the auto
restart function enabled. Refer to field setting
page 29
in the chapter
(1)
.
(2)
.
"[8] Option
setup,
"9.3. Field settings" on page
24.
"[8] Option
setup,
"9.3. Field settings" on page
24.
Installation manual
"[8-01]" on
"[8-01]" on
23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents