Lenovo System x3550 M5 Product Manual page 42

1u rack server
Hide thumbs Also See for System x3550 M5:
Table of Contents

Advertisement

Design to ASHRAE Class A3, ambient of 40 °C (104 °F), with relaxed support:
Supports cloud-like workload with no performance degradation acceptable (Turbo-Off).
Under no circumstance can any combination of worst case workload and configuration result in
system shutdown or design exposure at 40 °C.
Electrical:
Models with 1500 W AC Platinum power supplies:
200 - 240 (nominal) V ac; 50 Hz or 60 Hz; 8.35 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.14 kVA
Maximum configuration: 1.967 kVA
Models with 900 W AC Platinum power supplies:
100 to 127 (nominal) V ac; 50 Hz or 60 Hz; 10.3 A
200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 5.0 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.14 kVA
Maximum configuration: 1.194 kVA
Models with 750 W Platinum AC power supplies:
100 to 127 (nominal) V ac; 50 Hz or 60 Hz; 8.6 A
200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 4.2 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.14 kVA
Maximum configuration: 1.015 kVA
Models with 750 W Titanium AC power supplies:
200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 4.2 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.14 kVA
Maximum configuration: 0.965 kVA
Models with 550 W AC power supplies:
100 to 127 (nominal) V ac; 50 Hz or 60 Hz; 6.5 A
200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 3.3 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.14 kVA
Maximum configuration: 0.732 kVA
Models with -48Vdc 900 W power supplies:
-48 - -60 (nominal) V dc; 25.8 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.14 kVA
Maximum configuration: 1.237 kVA
BTU output:
Minimum configuration: 461 Btu/hr (135 watts)
Maximum configuration: 6667 Btu/hr (1954 watts)
Noise level:
6.6 bels (operating)
6.4 bels (idle)
System x3550 M5
42