Default Heating Curve Setting - Mitsubishi HMA100V User Manual

Air to water heat pump hydrolution
Hide thumbs Also See for HMA100V:
Table of Contents

Advertisement

Comfort setting heating

Default Heating curve setting

The basic heating is set using menu 2.1.2 and with the "Heating
curve offset" knob.
If the room temperature does not reach the target, readjustment
may be necessary.
If you do not know the correct settings, use the basic data from
the automatic heating control system diagram on the right.
9
Heating curve
2 . 1 . 2
Menu 2.1.2 Heating curve
Heating curve offset for system 2 can be made in menu 3.1
NOTE
Wait one day between settings so as to stabilise the
temperatures.
10
Offset heating curve
Setting with diagrams
The diagram shows the relation between the outdoor temperature
in the area and the target supply water temperature of the heating
system. This is set under menu 2.1.2, "Heating curve". Limitations,
which are not in the diagrams, can be set in the control system's
permitted min and max temperatures. (See menu 2.1.4 and 2.3 as
well as 3.3 and 3.4)
Heating curve offset -2
C
70
60
50
40
30
+ 5
10
0
Outdoor temperature
- 5
FÖRSKJUTNING
VÄRMEKURVA (-2)
OFFSET HEAT CURVE
Heating curve offset 0
C
70
60
50
40
30
+ 5
10
0
- 5
Outdoor temperature
FÖRSKJUTNING
VÄRMEKURVA (0)
OFFSET HEAT CURVE
Heating curve offset +2
C
70
60
50
40
30
+ 5
10
0
- 5
Outdoor temperature
FÖRSKJUTNING
VÄRMEKURVA (+2)
OFFSET HEAT CURVE
HEATING CURVE
VÄRMEKURVA
15 14 13 12
11
10
- 10
- 20
- 30
- 40
UTETEMPERATUR
HEATING CURVE
VÄRMEKURVA
15 14 13 12
11
10
- 10
- 20
- 30
- 40
UTETEMPERATUR
HEATING CURVE
VÄRMEKURVA
15 14 13 12 11
10
9
8
7
6
5
4
3
2
1
- 10
- 20
- 30
- 40
UTETEMPERATUR
9
8
7
6
5
4
3
2
1
C
9
8
7
6
5
4
3
2
1
C
C