Chapter 7 Setpoint

The setpoint menu is normally accessed from the Base Display by a klicking on the encoder
knob.
If you wish to change the displayed value, klick on the knob again and the change indicators
will start to flash to show that you are now in change mode. Twist the knob, clockwise to
increase the value, counter-clockwise to decrease.
When the desired value is shown, klick on the knob to acknowledge. To return to the Base
display, twist the knob.
For configurations involving a single output signal the setpoint is the starting point for the
output signal.
For configurations involving two diverging output signals with neutral zone (heating –
cooling) the setpoint is placed in the middle of the neutral zone.
For configurations involving two outputs without neutral zone (heating – heating, cooling –
cooling, heating – damper or cooling – damper) the setpoint value is the starting point for the
first sequence (Y2)
22