Vision OPLC V130-33-TA24 Installation Manual page 8

Table of Contents

Advertisement

Analog input wiring, current (2/3-wire)
Shields should be connected at the signal's source.
The 0V signal of the analog input must be connected to the controller's 0V.
Thermocouple
Thermocouple 0: use Input 9
as negative input and 10 as positive.
Thermocouple 1: use Input 7
as negative input and 8 as positive.
RTD
PT100 (Sensor 0): use Input 9 and 10, related to CM signal.
PT100 (Sensor 1): use Input 7 and 8, related to CM signal.
4 wire PT100 can be used by leaving one of the sensor leads unconnected
8
Analog Input
Analog input wiring, current (4-wire), voltage
Type Temp. Range
mV
-5 to 56mV
200 to 1820˚C
B
(300 to 3276˚F)
-200 to 750˚C
E
(-328 to 1382˚F)
-200 to 760˚C
J
(-328 to 1400˚F)
-200 to 1250˚C
K
(-328 to 2282˚F)
-200 to 1300˚C
N
(-328 to 2372˚F)
0 to 1768˚C
R
(32 to 3214˚F)
0 to 1768˚C
S
(32 to 3214˚F)
-200 to 400˚C
T
(-328 to 752˚F)
Vision™ OPLC™ Installation Guide
Wire Color
ANSI (USA) BS1843 (UK)
+Grey
+None
-Red
-Blue
+Violet
+Brown
-Red
-Blue
+White
+Yellow
-Red
-Blue
+Yellow
+Brown
-Red
-Blue
+Orange
+Orange
-Red
-Blue
+Black
+White
-Red
-Blue
+Black
+White
-Red
-Blue
+Blue
+White
-Red
-Blue
Unitronics

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents