CAN BUS NETWORK CONNECTION

When making the data interface connection (CANH and CANL signals) use an unscreened cable with a
twisted pair (cross-section 0.25/ 0.35 mm
2
AWG 22/24, impedance 100/150 ohm).
The maximum total length of the data signal cable should be no more than 100 m.
Activate the terminator at the first and last device connected to the network.
If there is only one device, the terminator does not need to be activated.
An example of a network connection is given below:
SBC 1950
SBC 1950
ADVANCED
ADVANCED
*
*
*
PLUS
PLUS
TEMPERATUR
CURRENT
LCD
(Unit 1)
(Unit 2)
BATTERIES
SENSOR
TERMINAL
SENSOR
*
Optional
devices.

OPERATION

When the battery charger is switched on, all the LEDS on the front panel will light up for a short period. After
that the battery charger will place itself in the optimum charging mode to best suit the batteries or load
connected.
The battery charger has a loading characteristic of the IU
U type.
0
The SBC battery chargers can also be used as a power supply, that is, with batteries disconnected.
We suggest you use the battery charger in this mode only occasionally and not for ordinary use. However,
avoid connecting high inductive loads (e.g. high powered motors) with the batteries disconnected as it you
could cause damage to the equipment.