LG RCWFL Series Installation Manual page 30

Water-cooled oil free inverter centrifugal chiller
Table of Contents

Advertisement

30
Inspection
Check if there is any damage to the parts attached on the product or control devices during delivery or transportation.
Check if there is any problem for spare part or separately packed parts.
Environment Conditions
Check if the installation status or environment is the same as the table shown below.
Item
Power supply
Power Frequency
Number of Power phase
Control power
Controller power
Storage temperature
Working temperature
Working humidity
Surrounding environment
Elevation vibration
Controller contact Output capacity
Controller contact Input capacity
Momentary blackout
compensation
Specification
380Vac, 440Vac
50/60Hz
3Phase
220/380/440Vac,3Ph
20Vac,1PH,50/60Hz
-10 °C ~ 60 °C
5 °C ~ 40 °C
25°C, 20% ~80%RH,
No dew condensation
No corrosive gas, flammable gas, oil
residue, dust, etc.
Altitude of 1000 m or below
5.9 m/sec²(=0.6g) or below
Load below 250 Vac, 3 A, Available to
connect load below 30 Vdc, 1 A
Zero voltage contact input
Controller : 100 mS or below
Remarks
It is the user's option.
May change depending on the power
supply of the customer.
It is the user's option.
It is the user's option.
It is the user's option.
May change depending on power supply
of the customer
- No-voltage "A" contact output
- Power (20 Vdc, 10 mA) applied from
the controller.
- Do not apply power from the outside.