BPS-602 - NAC Power Extender Overview: The Mircom BPS-602 is an extremely cost effective 6.5 amp remote power supply/battery charger. It may be connected to any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC such as strobes and horns) expansion support to meet ADA requirements.
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor dry use only. ground Carefully review: Application Guide for BPS-602, BPS-802, BPS-1002 Power Supply Specifications (pg. 3) Stand-by Specifications (pg. 3)
Page 4
(horns) to be silenced while visual notification appliances (strobes) continue to operate. The FACP must be capable of a visual annunciation to the silencing status of the output or zone(s) to which the BPS-602 (NAC Power Extender) is connected. Sync Mode Selection Table:...
Page 5
*Note: The BPS-602 will only synchronize horns, horn/strobes and strobes that contain synchronization capability. Contact signal manufacturer for more detailed info (see Appendix A.4, pg. 12). The same synchronization mode must be selected for all outputs Amount of Notification Appliances per NAC:...
The green input LEDs will be off (normal condition). To reset the memory depress the reset button (Fig. 2c, pg. 7). The LED(s) will extinguish. Note: If indicating circuits have been restored, memory reset is not required for normal operation of the unit. - 6 - BPS-602...
Fuses: Check input fuse on the power supply board, replace if necessary. Input fuse rating is 5 amp @ 250V. Note: Maximum charging current is 650mA. Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed. - 8 - BPS-602...
Current per number of devices. Stand-by: 90mA 90mA BPS-602 (Current draw from battery) Alarm: 175mA 175mA BPS-602 Current 90mA 175mA Auxiliary Devices Refer to device manual for current ratings. Alarm/Stand-by Alarm/Stand-by Alarm/Stand-by Auxiliary Devices Current (must not exceed 1 amp) Refer to device manual for current ratings.
Appendix A - UL Listed Compatible Devices A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with BPS-602 AUX output. Max Standby Alarm Smoke Detector/Base Detector Type Current (mA) Current (mA) FenWal CPD-7021 (w/70-201000-005 Base) Ionization 0.10...
Page 11
System Sensor 6424 Projected Beam 28.4 System Sensor Beam 1224(S) Projected Beam 38.5 * Contact manufacturer for current draws A.2 Door Holders Table A-2 below lists door holders compatible with BPS-602 AUX output. Manufacturer Model Type Current (mA) Edwards DH150A Floor Mount...
(38.1mm) (117.22mm) (117.22mm) (38.1mm) Mircom is not responsible for any typographical errors USA - 4575 Witmer Industrial Estates, Niagara Falls, NY 14305, Canada - 25 Interchange Way, Vaughan (Toronto), ON L4K5W3, 888-660-4655 • fax: 888-660-4113 web site: www.mircom.com IIBPS-602 K23O...
Need help?