Mitsubishi Electric PLA-A12BA Service Manual page 17

Hide thumbs Also See for PLA-A12BA:
Table of Contents

Advertisement

10-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<
Malfunction-diagnosis method at maintenance service>
CHECK
CHECK
display
ON/OFF
TEMP
ON/OFF
button
FAN
AUTO STOP
AUTO START
MODE
VANE
CHECK LOUVER
CHECK
TEST RUN
min
button
SET
RESET
CLOCK
[Procedure]
1. Press the CHECK button twice.
Refrigerant
address
display
2. Press the temperature
Temperature
buttons.
button
3. Point the remote controller at the
HOUR
sensor on the indoor unit and
button
press the HOUR button.
h
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
17
• "CHECK" lights, and refrigerant
address "00" blinks.
• Check that the remote controller's
display has stopped before continuing.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit's DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermit-
tent buzzer sound, the operation lamp
blinks, and the error code is
output.
(It takes 3 seconds at most for error
code to appear.)
• The check mode is cancelled.
To be continued to the next page.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pla-a18baPla-a24baPla-a30baPla-a36baPla-a42ba

Table of Contents