Midea ABSEU-A4-1511 Service Manual page 29

Aurora on-off series
Table of Contents

Advertisement

resume the previous operation setting (not
including swing function) automatically after 3
minutes when power returns.
If the memorization condition is forced cooling
mode, the unit will run in cooling mode for 30
minutes and turn to auto mode as 24℃ setting
temp.
If AC is off before power off and AC is required
to start up now, the compressor will have 1
minute delay when power on. Other conditions,
the compressor will have 3 minutes delay when
restarts.
7.4.9 Refrigerant Leakage Detection
With this new technology, the display area will
show "EC" when the outdoor unit detects
refrigerant leakage.
When compressor is active, the value of the
Coil temperature of evaporator T2 has no
change or very little change.
7.4.10 8℃ Heating(optional)
When the compressor is running, the indoor fan
motor will run without anti-cold air function.
When the compressor is off, the indoor fan
motor is off .
7.4.11 Self clean(optional)
For heat pump models which are provided with
this function, after running in cooling or drying
mode, if the user press "Self Clean" button on
remote controller, firstly, indoor unit runs in fan
only mode for a while, then low heat operation
and finally runs in fan only again. This function
can keep the inside of indoor unit dry and
prevent breeding of mold.
7.4.12 Follow me(optional)
1)
If the indoor PCB receives the signal which
results from pressing the FOLLOW ME button
on remote controller, the buzzer will emit a
sound and this indicates the follow me function
is initiated. But when the indoor PCB receives
signal which sent from remote controller every
3 minutes, the buzzer will not respond. When
the unit is running with follow me function, the
PCB will control the unit according to the
temperature from follow me signal, and the
temperature
collection
temperature sensor will be shielded, but the
error detective function of room temperature
sensor will be still valid.
2)
When the follow me function is available,
the PCB will control the unit according to the
room temperature from the remote controller
and the setting temperature.
3)
The PCB will take action to the mode
change information from remote controller
signal, but it will not affected by the setting
temperature.
4)
When the unit is running with follow me
function, if the PCB doesn't receive any signal
from remote controller for 7 minutes or pressing
FOLLOW ME button again, the follow me
function will be turned off automatically, and the
temperature will control the unit according to
the room temperature detected from its own
room
temperature
temperature.
function
of
room
sensor
and
setting