Instructing The System User - Viessmann Vitoplex 100 PV1 Service Instructions Manual

Oil/gas boiler
Hide thumbs Also See for Vitoplex 100 PV1:
Table of Contents

Advertisement

Adjusting the burner
Rated heating
Pressure drop on the hot gas
output
side
kW
Pa
150
200
250
310
400
410
500
620
The minimum boiler water temperature for oil and gas
operation is 75 °C.

Instructing the system user

The installer should instruct the user in the operation of
the system.
Operating and service documents
1. Complete and detach the customer registration
card:
Hand system users their section for safekeeping.
Retain the heating contractor's section.
2. File all parts lists, operating and service instructions
in the folder and hand this over to the system user.
The installation instructions are no longer required
after the installation is complete and therefore do
not need to be retained.
(cont.)
mbar
60
0.6
120
1.2
130
1.3
230
2.3
250
2.5
250
2.5
230
2.3
310
3.1
Commissioning, inspection, maintenance
Safeguard the boiler return temperature (minimum
temperature) of 65 °C.
Set the minimum heating output for the base load
stage according to the conditions of the flue system.
Note that the flue system must be suitable for the low
flue gas temperatures that may occur.
In the event of frequent cycling in standby mode and
for partial loads below 40 %, we recommend the fol-
lowing:
Insulate the flue gas collector
Install a motorised flue gas damper
Set the minimum boiler runtime to 10 min
This extends the service life and reduces running
costs.