P U HZ - S HW 1 1 2 Y HA
SY MB OL
NAME
TB 1
Terminal B lock<Power Supply>
TB 2
Terminal B lock<Indoor/ Outdoor>
MC
Motor for Compressor
MF1, MF2
Fan Motor
21S4
Solenoid V alve (Four-Way V alve)
63H
High Pressure Switch
63L
Low Pressure Switch
63HS
High Pressure Sensor
TH3
Thermistor<Liq uid>
TH4
Thermistor<Discharge>
TH6
Thermistor<2-Phase Pipe>
TH7
Thermistor<Ambient>
TH8
Thermistor<Heat Sink>
TH32
Thermistor<Suction>
TH33
Thermistor<Ref. check>
TH34
Thermistor<Comp. Surface>
Linear Ex pansion V alve
LEV -A, LEV -B , LEV -C
ACL1, ACL2, ACL3, ACL4
Reactor
CY 1, CY 2
Capacitor
63H
63L
C. B .
MF1
1
CNF1
1
7
(WHT)
MS
TH33
3~
(Y LW)
MF2
1
CNF2
7
(WHT)
MS
3~
3
TRANS
2
1
CNDC
(PNK)
F2
CNAC
(WHT)
CNS
1
(WHT)
F1
3
1
3
4
TB 2
S1
S2
INDOOR
UNIT
S3
N. F.
TB 1
LI1
RED
L1
LI2
WHT
POWER
L2
SUPPLY
3N~
LI3
B LK
400V 50Hz
L3
NI
B LU
N
* 3 Ambient temp. of Z UB ADAN Flash Injection becomes effective.
The black sq uare( )indicates a switch position.
Ambient temp.
SW9 -3,4 * 4
Ambient temp.
3° C or less
ON
0° C or less
OFF
(lnitial setting)
1 2 3 4
* 4 SW9 -1 to 2 : Function Switch
OCH526C
P U HZ - S HW 1 4 0 Y HA
SY MB OL
CK
Capacitor
Rush Current Protect Resistor
RS
P. B .
Power Circuit B oard
TB -U/ V / W
Connection Terminal<U/ V / W-Phase >
TB -L1/ L2/ L3
Connection Terminal<L1/ L2/ L3-Power Supply >
TB -N
Connection Terminal
X 52CA
52C Relay
N. F.
Noise Filter Circuit B oard
LI1, LI2. LI3, NI
Connection Terminal<L1/ L2/ L3/ N-Power Supply >
LO1, LO2, LO3, NO
Connection Terminal<L1/ L2/ L3/ N-Power Supply >
GD1, GD3
Connection Terminal<Ground>
Converter Circuit B oard
CONV . B .
L1-A1/ IN
Connection Terminal<L1-Power Supply >
L1-A2/ OU
Connection Terminal<L1-Power Supply >
L2-A2/ OU
Connection Terminal<L2-Power Supply >
L3-A2/ OU
Connection Terminal<L3-Power Supply >
N-IN
Connection Terminal
CK-OU
Connection Terminal
LEV -A
63HS
M
TH33
TH32
TH7
TH6
TH3
TH4
TH34
3
1 2
1
4 1 2 2 1
1
3
2 1
1
5
1
TH32
TH7 / 6
TH3
TH4
63HS
TH34
LEV -A
(B LK)
(RED)
(WHT)
(WHT)
(WHT)
(RED)
(WHT)
1
3
63L
(RED)
1
3
5
63H
CN4
(Y LW)
(WHT)
1 2
CN2
(WHT)
1
7
1
LEV -C
2
7
F3
2
F4
1
3
1
21S4
(GRN)
21S4
TH8
3
7
2
P. B .
1
3 1 2
1 2
1
CN7
CN6
CN5
(WHT)
(WHT)
(WHT)
(RED)
B LK
WHT
RED
V
W
U
MS
3~
MC
CNAC1
(WHT)
1
3
1
CNDC
GD1
GD3
(PNK)
2
SW9 -3,4 * 4
Ambient temp.
ON
– 3° C or less
OFF
1 2 3 4
NAME
SY MB OL
C. B .
SW1
SW4
SW5
SW6
SW7
SW8
SW9
SWP
CN31
CNDM
CN51
SV 1/ CH
SS
CNM
LED1, LED2
F1, F2, F3, F4
X 51, X 52, X 54
LEV -C
LEV -B
M
M
3
5
5
* 1
* 1
1
3
1
5
5
CNV MNT
CNMNT
LEV -B
(WHT)
(WHT)
(RED)
* 3
1
14
CNM
(WHT)
CN31
1
5
3
(B LU
)
1
3
1
SV 1
3
1
3
SS
5
/ CH
(WHT)
(GRY )
2
7 1 2
CN2
CN4
(WHT)
RED
RED
RS
X 52CA
TB -N
CK
3
3
CONV . B .
1
2
CNAC2
CNCT
(RED)
(RED) 1 2
1
3
LO1
RED
LO2
WHT
LO3
B LK
NO
B LU
+
+
-
3
3
1
CNL
(B LU)
ACL4
SW9 -3,4 * 4
Ambient temp.
SW9 -3,4 * 4
ON
ON
– 6° C or less
OFF
OFF
1 2 3 4
NAME
Controller Circuit B oard
Switch<Manual Defrost, Defect History,
Record Reset, Refrigerant Address >
Switch<Test Operation >
Switch<Function Switch, Model Select >
Switch<Model Select >
Switch<Function Switch >
Switch<Function Switch >
Switch<Function Switch >
Switch<Pump Down >
Connector<Emergency Operation >
Connector<Connection for Option >
Connector<Connection for Option >
Connector<Connection for Option >
Connector<Connection for Option >
Connector<Connection for Option >
LED<Operation Inspection Indicators >
FUSE<T6.3AL250V >
Relay
When M-NET adapter is connected
5
CN5
(WHT)
5
1
M-NET ADAPTER
2
CN2M
CND
(WHT)
(WHT)
1
3
1
3
A B
S
TB 7
M-NET
M-NET ADAPTER
SY MB OL
NAME
TB 7
Terminal B lock<M-NET connection>
CN5
Connector<Transmission>
CND
Connector<Power Supply>
CN2M
Connector<M-NET communication>
* 1 MODEL SELECT
The black sq uare( )indicates
a switch position.
MODEL
SW6
ON
OFF
1 2 3 4 5 6 7
112Y
SW5-6 * 2
ACL1
ON
OFF
1 2 3 4 5 6
MODEL
SW6
ACL2
ON
OFF
1 2 3 4 5 6 7
ACL3
140Y
SW5-6 * 2
ON
OFF
1 2 3 4 5 6
* 2 SW5 -1 to 5 : Function Switch
1 2 3 4
8
8

Advertisement