Leak Check; High Altitude Derate; Pressure Switch; Conversion - Nordyne M3RL Series Installation Instructions Manual

Direct vent (sealed combustion) forced air gas furnaces m3rl series 90+ downflow condensing furnace
Table of Contents

Advertisement

Main
Blower
Control
Board
Inducer
Burner
Box
Gas
Valve
To Gas
Supply
Figure 22. Typical Gas Piping
If the test pressure is less than or equal to 1/2
psig (14 in. water column), the furnace must be
isolated from the gas supply line by closing the
manual shut-off valve.

Leak Check

After the gas piping to the furnace is complete,
all connections must be tested for gas leaks. To
check for leaks use only a soap and water solu-
tion or other approved method.

High Altitude Derate

The nameplate input rating for the furnaces
apply for elevations up to 4,000 feet above sea
level for US and Canada. If the elevation for the
furnace location is higher than 4,000 feet above
sea level, the furnace input must be derated by
using the appropriate orifice size listed in
Table 8.
NOTE: The density of air decreases with in-
creasing elevation above sea level. This re-
duces the quantity of combustion air drawn into
the furnace under normal operation and requires
the unit be derated by using smaller gas orifices
or lower manifold pressure.

CONVERSION

This furnace can be converted from the fac-
tory-equipped gas to either natural gas (for LP
gas ready models), or LP gas (for natural gas
ready models). Conversions must be made by
qualified service personnel, using only factory
authorized or approved parts. The required
conversion orifices are supplied with the fur-
nace.
DO NOT REMOVE OR DEFACE THE
ORIGINAL RATING PLATE.
The gas supply shall be shut off prior to
disconnecting the electrical power,
before proceeding with the conversion.
Alt. Gas
Line Entry
To Turn Off Fuel Supply to the Appliance:
1.
Set the room thermostat to "OFF" or its
lowest temperature setting.
2.
Turn OFF the main gas supply to the appli-
ance at the manual valve, outside of the
appliance casing.
3.
Remove the control access panel / lou-
vered door.
4.
Move the appliance gas valve lever/knob to
the "OFF" position.
5.
Turn OFF the electrical power to the appli-
ance.
CAPACITY OF BLACK IRON GAS PIPE (CU. FT. PER HOUR)
FOR NATURAL GAS (SPECIFIC GRAVITY - 0.60)
NOMINAL
BLACK IRON
PIPE DIAMETER
(in.)
1/2
3/4
1
1 1/4
1 1/2
The cubic feet per hour listed in the table above must be greater than
the cubic feet per hour of gas flow required by the furnace.
To determine the cubic feet per hour of gas flow required by the furnace,
divide the input rate of the furnace by the heating value of the gas:
Cubic Feet
Per Hour Required
Table
7. Capacity of Black Iron Gas Pipe
(cu. ft. per hour) for Natural Gas
!
WARNING:
CAUTION:
!
LENGTH OF PIPE RUN
(feet)
10
20
30
40
50
130
90
75
65
55
280
190
150
130
115
520
350
285
245
215
1050
730
590
500
440
1600 1100
890
760
670
Input To Furnace (Btu/hr)
=
Heating Value of Gas (Btu/Cu. Ft.)
(specific gravity = .60)
60
70
80
50
45
40
105
95
90
195
180
170
400
370
350
610
560
530
21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

M3 rl-060M3 rl-080

Table of Contents