Kenmore 153.559400 Use & Care Manual page 15

Table of Contents

Advertisement

Temperature-Pressure
Relief Valve
Explosion
Harzard
Temperature-pressure
relief
valve must comply with ANSI
Z21.22-CSA
4.4 and ASME
code.
• Properly sized temperature-
pressure relief valve must be
installed in opening provided.
• Do not plug, block, or cap the
discharge
line.
• Failure to follow this warning
can result in excessive
tank
pressure, serious injury or
death.
This heater is provided with a properly certified combination
temperature - pressure relief valve by the manufacturer.
The valve is certified by a nationally recognized testing laboratory
that maintains
periodic
inspection
of production
of listed
equipment as meeting the requirements for Relief Valves for Hot
Water Supply Systems, ANSI Z21.22 and the code requirements
of ASME.
If replaced, the valve must meet the requirements of local codes,
but not less than a combination temperature and pressure relief
valve certified as indicated in the above paragraph.
The valve must be marked with a maximum set pressure not to
exceed the marked hydrostatic working pressure of the water
heater (150 psi = 1,035kPa) and a discharge capacity not tess than
the water heater input rate as shown on the model rating plate.
For safe operation of the water heater, the relief valve must not
be removed from its designated opening nor plugged.
The temperature-pressure
relief valve must be installed directly
into the fitting of the water heater designed for the relief valve.
Position the valve opening downward
and provide tubing so
that any discharge
wilt exit only within 6 inches (15.3 cm)
above, or at any distance below the structural floor, see Figure
16. Be certain that no contact is made with any live electrical
part. The discharge opening must not be blocked or reduced in
size under any circumstances.
Excessive length, over 30 feet
(9.14 m), or use of more than four elbows can cause restriction
and reduce the discharge capacity of the valve.
No valve or other obstruction is to be placed between the relief
valve and the tank. Do not connect tubing directly to discharge
drain unless a 6 inch air gap is provided.
To prevent bodily
injury, hazard to life, or property damage, the relief valve must
be allowed to discharge water in quantities should circumstances
demand. Ifthe discharge pipe is not connected to a drain or other
suitable means, the water flow may cause property damage.
f%
HOT
WATER
I
I
COLD
WATER
__
OUTLET
L
J
___
INLET
DRAFT HOOD --
i
DRAIN
VALVE
/
\
TEMPERATURE
- PRESSURE
RELIEF
VALVE
(OPTIONAL
TOP
T&P
RELIEF
VALVE
NOT
SHOWN)
l'_ DISCHARG E PIPE
(Do not cap or plug)
_._T
6" MAXIMUM
AIR
GAP
FLOOR
DRAIN
FIGURE
16.
Water Damage Hazard
• Temperature-pressure
relief valve discharge
pipe must terminate at adequate drain.
The Discharge Pipe:
• Shall not be smaller in size than the outlet pipe size of the
valve, or have any reducing couplings or other restrictions.
• Shall not be plugged or blocked.
• Shall be of material listed for hot water distribution.
Shall be installed so as to allow complete drainage of both the
temperature-pressure
relief valve, and the discharge pipe.
Shall terminate a maximum of six inches above a floor drain
or external to the building. In cold climates, it is recommended
that the discharge pipe be terminated at an adequate drain
inside the building.
• Shall terminate at an adequate drain.
• Shall not have any valve between the relief valve and tank.
I7:1 [el ;|
Water
temperature
over
125°F
(52°C) can cause severe burns
instantly resulting in severe injury
or death.
Children,
the
elderly,
and
the
physically
or mentally
disabled
are at highest riskforscald
injury.
Feel
water
before
bathing
or
showering.
Temperature
limiting valves
are
available.
Read instruction
manual for safe
temperature setting
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

153.559500

Table of Contents