I N S T R U C T I O N S
DIGITAL THERMOSTAT
1.Introduction
To sure the correct use of the device,please read the instruction manual
beforehand. After reading the manual,make sure to keep it to hand.
2.Limit on Application
The product is not designed nor manufactured for an use in such equipment or system
that is intended to be used under such circumstances that may affect human life.
For application requiring extreme high reliability,please contact the Company first.
3.Safety Precaution
Failure in observing the following could result in fires,
WARNING
electrification or breakdown of the device.
●Make sure to cut off power before wiring.Otherwise,there is a possibility
to have an electric shock.
●Do not install the device at the place where is high humidity,water and oil
ingress, because it will cause damage,heat-up and ignition.
●Observe not to decompose,repair and modify by other than the Company.
To touch with the internal parts may cause an electric shock and defects.
4.Handling Precaution
Failure in observing the following could result in injuries
CAUTION
of operators, or damage and malfunction of the device.
To avoid damages,malfunctions and grievances,make sure to attend to the
following matters.
1)For Thermostat main unit
●Do not install the humidistat in the following environments.
・Places with severe mechanical vibration or shocks.
・Dusty places.
・Place the ambient temperature of thermostat is over the range of -10 to 50℃.
・Near device generating storong high-frequency noises.
●Storage and Transportation
・Do not drop and give damages the thermostat during storage and transportation
because the humidistat itself is a precision mechanical equipment.
2)For Temperature Sensor
●Sensor is recommended to be installed at aplace where air flow exists and
representative humidity can be sensed.
●Do not install the following locations.
・Where rain fall, dew or direct sunlight is expected.
・Where dust or corrosion gas is expected.
(Especially Humidity Sensor can not be installed near aceton,ammonia
or organic gas is expected.)
・If there is large difference between surface temp.of inside wall and
room temp.the sensor should be installed with heat insulator as wall
temp. affect humidity sensor.
・Sensor line should be isolated from power and lead lines to prevent
from induction noise influence.
5.Operation check
Install and calibrate the product correctly and then check its operation to
confirm correct function of the whole system when using.
Failure in observing the following could result in injuries
!
CAUTION
of operators, or damage and malfunction of the device.
●If the device is used in equipment that generates electromagnetic waves, double-check
the operation to detect any malfunction. In order to avoid the influence of
electromagnetic waves, do not confront the device with the electro-magnetic wave
generating component of the equipment.
●When the power distribution is resumed after an electric power failure, the device
resets itself automatically, reading out the operation mode, preset values, and
calibration values in memory. For safety precautions, however, confirm that the
whole system including the device is working properly.
LE-10 JUN.2004
2STEP
6.Specifications
1)Thermostat
・Power Voltage
:85VAC∼264VAC
・Power Consumption
:5VA(approx.)
・Allowable Relay Output
:AC250V 10A(Resistance Load)
:AC250V 6A(Inductive Load. P.F.COSφ=0.7)
:AC250V 3A(Inductive Load. P.F.COSφ=0.4)
・Storage Temp.:-20℃∼70℃
・Weight
: 0.2kg(approx.)
2)Temperature Sensor
・Type
:TEK-83H609
:TEK-83H601
・Ambient Temp.
:TEK-83H609 : -55℃∼ 80℃
:TEK-83H601 : -40℃∼110℃
・Sensor Storage Temp.
:TEK-83H609 : -55℃∼80℃
:TEK-83H601 : -40℃∼115℃
・Weight
:0.02kg(approx.)
Display Range
Catalog No.
(℃)
ULE-SD12-011
-55∼40
ULE-SD22-011
0∼110
Temperature Indication:0.5℃ Step、Temperature Set:0.5℃ Step
7.Dimensions
●Thermostat
THERMO EYE-U
℃ ℃
O N 2 O N 1
SEL
OFF
SET 1
ON
OFF
SET 2
ON
ENT
Fixing Screw
77
●Temperature Sensor
TEK-83H609
Color of lead wire : Blue
TEK-83H601
Color of lead wire : Black
30
●Panel Fittings
2 pcs.(Standard Accessory)
Factory Settings
Set Range
STEP1
(℃)
OFF(℃)
ON(℃)
OFF(℃) ON(℃)
-50∼30
0
2
0∼100
50
52
8
52
2000
●Sensor holder
1 pcs.(Standard Accessory)
13
27
(52)
2-φ4.2HOLES
STEP2
1
3
51
53
18

Advertisement

loading

Summary of Contents for Saginomiya type ule

  • Page 1 6.Specifications I N S T R U C T I O N S 1)Thermostat ・Power Voltage :85VAC∼264VAC ・Power Consumption :5VA(approx.) ・Allowable Relay Output :AC250V 10A(Resistance Load) DIGITAL THERMOSTAT 2STEP :AC250V 6A(Inductive Load. P.F.COSφ=0.7) :AC250V 3A(Inductive Load. P.F.COSφ=0.4) ・Storage Temp.:-20℃∼70℃ ・Weight :...
  • Page 2 8.Installation 9.Wiring 1)Mounting of Humistat Make sure to cut off the power before wiring,and start it after safety check. 1-1) Remove the front cover Further,apply the power to the ULE after make sure to re-check the wiring and close the case with fixing screw. Wiring method ・Make sure to connect with M3.5 crimp terminal.
  • Page 3 ON. In case of heating mode, the temp. setting point of Type ULE can lock keys to prevent wrong operations by pressing [UP] key and [ENT] OFF should be higher than that of ON.
  • Page 4 How to perform Calibration like and other causes beyond the control of the Company. Type ULE turns into Calibration mode by pressing [UP] key and [DOWN] key simultaneously Warranty described in this paragraph means the warranty for the Product itself and dose not include warranty for any consequential damage arising out of or occasioned for about 8 seconds.If no keys are pressed for about 10 seconds, the device turns into...