American Standard AUY060R9V3W Service Facts page 12

Table of Contents

Advertisement

Service Facts
*UY100R9V4W FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
AIRFLOW
SETTING
LOW
MEDIUM LOW
HEATING
1ST
STAGE
MEDIUM **
HIGH
LOW
MEDIUM LOW
HEATING
2ND
STAGE
MEDIUM **
HIGH
NOTES:
* First letter may be "A" or "T"
** Factory setting
*UY100R9V4W FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOOR
AIRFLOW
UNIT SIZE
SETTING
(TONS)
LOW
(350 CFM/TON)
NORMAL
2.5
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
3.0
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
3.5
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
4.0
(400 CFM/TON)
HIGH
(450 CFM/TON)
NOTES: *First letter may be "A" or "T"
1. At Continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.
2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting;
NORMAL airflow (400 cfm/ton) is typical setting;
HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.
12
DIP SWITCH SETTING
SW 7
SW 8
CFM
ON
ON
TEMP. RISE
WATTS
CFM
OFF
ON
TEMP. RISE
WATTS
CFM
ON
OFF
TEMP. RISE
WATTS
CFM
OFF
OFF
TEMP. RISE
WATTS
CFM
ON
ON
TEMP. RISE
WATTS
CFM
OFF
ON
TEMP. RISE
WATTS
CFM
ON
OFF
TEMP. RISE
WATTS
CFM
OFF
OFF
TEMP. RISE
WATTS
DIP SWITCH SETTING
SW 1
SW 2
SW 3
ON
ON
OFF
ON
ON
OFF
ON
ON
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
1st Stage Capacity =
2nd Stage Capacity =
EXTERNAL STATIC PRESSURE
0.1
0.3
873
893
64
63
100
145
971
997
58
56
115
170
1136
1146
49
49
160
230
1258
1298
44
43
225
300
1260
1304
68
66
213
305
1464
1471
59
59
315
405
1631
1678
53
51
450
570
1846
1867
47
46
640
760
SW 4
0.1
CFM
808
ON
WATTS
75
CFM
938
OFF
WATTS
100
CFM
1058
OFF
WATTS
150
CFM
1004
ON
WATTS
120
CFM
1141
OFF
WATTS
170
CFM
1336
OFF
WATTS
250
CFM
1153
ON
WATTS
180
CFM
1390
OFF
WATTS
285
CFM
1575
OFF
WATTS
400
CFM
1388
ON
WATTS
290
CFM
1610
OFF
WATTS
415
CFM
1847
OFF
WATTS
630
62,000
93,000
0.5
0.7
900
899
62
62
195
240
1006
1022
56
55
220
280
1165
1180
48
47
295
365
1319
1328
42
42
390
450
1329
1334
65
65
380
460
1478
1478
58
58
485
560
1690
1579
51
55
670
645
1794
1644
48
52
770
700
EXTERNAL STATIC PRESSURE
0.3
0.5
0.7
824
840
835
125
170
210
963
959
964
160
205
255
1100
1121
1136
200
265
330
1010
1027
1044
175
230
285
1190
1214
1229
245
310
380
1375
1387
1388
330
410
480
1206
1230
1239
250
320
395
1418
1439
1441
465
445
515
1606
1632
1596
495
590
645
1423
1444
1444
360
440
515
1641
1666
1607
515
635
650
1863
1816
1687
735
780
720
Page B-651-438
0.9
902
62
290
1029
54
335
1184
47
425
1286
44
490
1317
65
510
1350
64
540
1419
61
585
1498
57
650
0.9
830
250
975
310
1142
395
1050
345
1234
450
1384
545
1244
460
1373
540
1445
590
1390
540
1449
595
1532
665

Hide quick links: