Electrical Data - Daikin RZQ100B8W1B Technical Data Manual

Hide thumbs Also See for RZQ100B8W1B:
Table of Contents

Advertisement

3

Electrical data

RZQ-BW1
Unit combination
Indoor unit
Outdoor unit
1
3
SYMBOLS
MCA
: Min. Circuit Amps (A)
TOCA
: Total Over Current Amps (A)
MFA
: Max. Fuse Amps (See note 7) (A)
MSC
: MSC means the max. current during the
starting of compressor. (A)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor (A)
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
kW
: Fan Motor Rated Output (kW)
9
• Outdoor Units • R-410A • RZQ100-140B8W1B
Power supply
Hz-volts
Vol t age range
MCA TOCA MFA MSC
NOTES
1 RLA is based on the following conditions:
Power supply: 50Hz 230V
Cooling
Indoor temperature 27°CDB/19°CWB
Outdoor temperature 35°CDB
2 TOCA means the total value of each OC set
3 Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed operation range limits
4 Maximum allowable voltage unbalance between phases is 2%
5 MCA represents maximum input current., MFA represents capacity which may accept MCA
(next lower standard fuse rating, min.15A)
6 Select wire size based on the larger value of MCA or TOCA
7 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
8 For more details concerning conditional connections, see http://extranet.daikineurope.com, select ''E-Data Books''. Finally, click on the document title of your choice.
• Split Sky Air • Outdoor Units
Comp.
OFM
IFM
RLA
kW
FLA
kW
3D048638C
Heating
Indoor temperature 20.0°CDB
Outdoor temperature 7.0°CDB/6.0°CWB
FLA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rzq125b8w1bRzq140b8w1b

Table of Contents