Installation

12 - 1 Installation Method

RZQSG71LV1
A. Non stacked installation
1
12
B. Stacked installation
1. Obstacles exist in front of the outlet side
About 100mm is required as the dimension for laying the upper outdoor unit's drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
C. Multiple-row installation
1. Installation of one unit per row
Relation of dimensions of H, A, and L are shown in the table below.
0 < L ≤ 1/2 H
L ≤ H
1/2 H < L
H < L
Installation impossible
36
• Outdoor Unit • Optimized for seasonal efficiency • RZQSG-LV1
Do not stack more than one unit.
L
A
150 (250)
200 (300)
®
• Split - Sky Air
• Outdoor Unit
2. Obstacles exist in front of the air inlet
2. Installing multiple units (2 units or more) in
lateral connection per row
Legend
Unit: mm
Suction side obstacle
Discharge side obstacle
Left side obstacle
Right side obstacle
Top side obstacle
Obstacle is present
1
In these cases, close the bottom of the
installation frame to prevent discharged air from
being bypassed.
2
In these cases, only 2 units can be installed.
This situation is not allowed.
Figures between ( ) indicate the
dimensions only for the 100-125-140
class models.
3TW26739-4