5-2. RAS-07SKHP-E / RAS-07S2AH-E

Cooling
0.39m
Heating
(Connecting pipe)
∅9.52
O.D.:9.52mm
P
Packed valve
(∅9.52)
Heating
Cooling
4-way valve
Heating Cooling Compressor
Cooling
Heating
50Hz
Standard
Heating
Overload
Low temperature
Standard
Cooling
Overload
Low temperature
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
Indoor unit
Heat exchanger
Cross flow fan
PH108X1C-4DZDN2
Accumulator
Heat exchanger
Propeller fan
Outdoor unit
Standard
Surface temp. of heat
exchanger interchanging
pressure P
(MPaG)
1.32
1.93
1.14
0.52
0.68
0.32
– 12 –
T1
Packed valve
(∅6.35)
Capillary tube
∅1.0x1000S
(2 pcs.)
Refrigerant
R-22 : 0.64 kg.
Mark(
)means check points of Gas Leak.
Fan speed
(indoor)
pipe T1 (°C)
35.0
50.0
30.0
13.0
18.0
7.0
FILE NO. SVM-07023
0.49m
(Connecting pipe)
∅6.35
O.D.:6.35mm
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor
High
20/–
7/6
Low
27/–
24/18
High
20/–
–10/–10
High
27/19
35/24
High
32/23
43/26
Low
21/15
21/15