2. All heater packages covered by this manual are
factory wired for single supply circuit. The
following heater packages are field convertible to a
dual supply circuit if required or desired:
EHWA03-A15
EHWH30-A10
EHWH36-A10
EHWH36-A15
3. To convert the above heater packages to dual
circuit configuration before installation, loosen four
(4) screws holding jumper bar in place. Remove
jumper bar. Circuits A + B are now identified on
the heater package. See Figure 1.
Wire should be sized to the minimum circuit
ampacity as specified on the serial plates of units
that accept these heater package for circuits
A + B.

INSTALLATION

1. Disconnect all power to unit before installation.
WARNING
Disconnect all power to unit before installing
heater package. Hazard of electrical shock.
Failure to disconnect power could result in injury
or death.
2. Before installation, check unit serial plate to insure
that the heater package model that you intend to
install is listed as a heater package suitable for use
with the unit.
Under no circumstance shall a heater package be
installed in a unit if the model number of the heater
package does not appear on the unit serial plate.
WARNING
Install only heater packages listed on unit serial
plate. Hazard of fire or electrical shock. Failure
to install listed heater package could result in
fire, injury or death.
Manual
2100-268
Page
6
3. Remove electric heater access panel and control
panel cover, both inner and outer. See Figure 2.
4. All heaters are installed with the thermal cutoffs
positioned to the top of the unit. Install heat
strip(s) through heater access opening. Position
heat strip support rod in heater support hole 1, 2 or
3 as indicated in Table 1 and Figure 3.
On heater packages with two (2) heat strips, install
9KW heater first in position closest to the outlet air
frame. See Figure 4E.
5. Install heater control base into top of control panel
as shown in Figure 4. Secure with four (4) sheet
metal screws provided.
6. Plug mail six (6) pin connector into mating
connector mounted in control panel. See

Figure 5.

7. Connect red compressor supply lead to L1 of
terminal block. Connect black compressor supply
lead to L2 of terminal block. If three phase,
connect yellow supply lead to L3 of terminal block.
See Figure 4 and wiring diagram.
8. Route wires from heater control base up through
raceway in top right corner of control panel to the
heaters. See Figure 5.
9. Wire heater package per wiring diagram supplied
with this heater package. All wires are stamped
oath wire numbers that correspond with terminal
numbers on the wiring diagram and stamped
numbers on the heat strip. Limit switch wires are
terminated with insulate quick connect terminals.
See Figure 4.
10. Attach adhesive wiring diagram directly above unit
wiring diagram on inner control panel cover.
11. Recheck all wiring. Break out appropriate circuit
breaker tabs on inner control panel cover to allow
trip lever to protrude. Replace control panel and
heater access panels.
12. Resupply power to the unit and check for proper
operation.
13. Remark serial plate with self-adhesive label
attached to the front of this manual. See Figure 6.