Standard Performances In Heating Mode As-7M5 - Ferroli 150.4 Technical Manual

Air water heat pumps with helical fans
Table of Contents

Advertisement

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - R407C

Standard performances in heating mode AS-7M5

MODEL
Tw
35
40
150
45
50
35
40
165
45
50
35
40
180
45
50
35
40
205
45
50
35
40
230
45
50
35
40
260
45
50
35
40
285
45
50
35
40
315
45
50
Tw= Outlet water temperature in C
The standard performances refer to a 5 C temperature difference between the water entering and leaving the plate-type heat exchanger, out-
door air with 87% relative humidity and to operation of the unit with all the fans to top speed. A 0.44 x 10-4 m2 K/W fouling factor has also
been considered with the unit installed at zero meters above sea level (Pb = 1013mbar).
NOTE
For air temperatures of less than 7 C, the heating capacity is declared without considering the effect of the thawing cycles, strictly correlated with
the humidity in the outdoor air.
-5
0
kWf
kWa
kWf
105
40,0
131
108
45,4
132
110
50,8
132
112
57,7
133
115
43,4
143
118
49,3
144
120
55,2
145
123
62,7
146
126
47,8
157
129
54,3
158
132
60,8
159
135
69,2
160
145
54,7
181
149
62,3
183
153
69,8
184
157
79,5
186
166
60,1
204
170
68,1
206
174
76,0
208
178
86,2
211
185
66,4
225
190
74,9
228
194
83,3
231
199
94,1
234
213
74,2
259
219
83,6
263
224
93,0
266
229
105
269
235
82,5
286
241
92,9
289
246
103
293
252
117
296
kWf = Net heating output (kW).
OUTDOOR AIR TEMPERATURE (°C D.B.)
5
kWa
kWf
kWa
40,9
157
41,8
46,4
156
47,4
51,9
155
53,3
58,9
152
60,4
44,3
171
45,2
50,3
170
51,3
56,2
169
57,7
63,9
166
65,3
48,7
187
49,6
55,3
187
56,3
61,9
186
63,3
70,4
183
71,8
55,5
216
56,3
63,2
216
64,1
70,8
216
72,1
80,6
213
81,9
60,9
241
61,7
69,0
242
70,0
77,2
243
78,7
87,6
240
89,3
67,2
265
68,0
76,0
266
77,1
84,7
267
86,6
95,9
265
98,1
75,0
246
75,9
84,8
279
86,1
94,6
314
96,7
107
355
110
83,5
336
84,5
94,3
338
95,7
105
339
108
119
336
122
7
10
kWf
kWa
kWf
167
42,2
183
165
47,8
180
160
53,3
175
159
60,9
172
182
45,6
199
181
51,7
197
175
57,7
191
175
65,9
189
200
49,9
218
198
56,7
216
192
63,4
210
193
72,3
208
230
56,7
251
229
64,4
249
222
72,3
243
224
82,3
242
257
62,0
279
256
70,4
278
250
79,4
273
252
90,0
272
281
68,3
305
282
77,5
304
276
87,8
300
278
98,9
299
324
76,3
352
324
86,6
351
318
98,0
346
320
110
345
357
84,8
387
357
96,3
386
350
109
381
353
123
380
kWa = Power input of compressors (kW)
15
kWa
kWf
kWa
42,8
208
43,7
48,4
204
49,4
54,0
200
55,2
61,5
195
62,6
46,1
227
47,0
52,3
223
53,3
58,4
219
59,5
66,5
214
67,5
50,5
249
51,4
57,3
244
58,3
64,1
240
65,2
72,9
236
73,9
57,2
286
58,0
65,0
282
65,8
72,8
279
73,7
82,9
275
83,8
62,5
317
63,3
71,0
314
72,0
79,9
311
80,8
90,7
308
91,9
68,8
345
69,6
78,2
343
79,3
88,3
340
89,1
99,9
338
101
77
398
78
87
395
89
99
392
99
112
389
113
85
438
86
97
435
98
110
432
111
124
428
126
17