Direct Venting; Removal Of Existing Furnaces From Common Vent Systems; Combustion-Air And Vent Piping - Carrier 58MVP080 Installation, Start-Up, And Operating Instructions Manual

111 series
Table of Contents

Advertisement

(1.) Remove 2 screws securing the control box to furnace
blower shelf.
(2.) Remove and discard 2 factory supplied leads from
control center EAC terminals.
(3.) Strip EAC power leads insulation approximately 1/8-
in.
NOTE: The control center EAC terminals are sized for 12 gage
maximum, solid or stranded wire.
(4.) Route EAC leads through right-hand wire grommet.
(5.) Insert EAC stripped leads into control center EAC
terminals by depressing terminals arm with a screw-
driver or finger. (See Fig 26.)
Fig. 26—EAC Terminals on Control Center
(6.) Reinstall control box to furnace blower shelf using 2
screws removed earlier.
2. Humidifier (HUM)
Screw terminals (HUM and Com) are provided for 24-v
humidifier connection. (See Fig. 23.) HUM terminal is ener-
gized with 24v (0.5-amp maximum) after inducer motor
prepurge period.
NOTE: A field-supplied, 115-v controlled relay connected to
EAC terminals may be added if humidifier operation is desired
during blower operation.
3. Dehumidification (DH)
A 1/4-in. male quick-connect terminal is provided on control
center to attach a normally open (N/O) humidistat contact
when dehumidification is desired. (See Fig. 25.) Connect
humidistat to thermostat R terminal and DH terminal on
control center. A 15 percent reduction of cooling airflow or
constant fan airflow will occur when DH terminal is energized
and a single- or 2-speed "call for cooling" is received.

DIRECT VENTING

The 58MVP Furnaces require a dedicated (one 58MVP furnace
only) direct vent system. In a direct vent system, all air for
combustion is taken directly from outside atmosphere, and all flue
products are discharged to outside atmosphere.
Step 1—Removal of Existing Furnaces from
Common Vent Systems
If furnace being replaced was connected to a common vent system
with other appliances, these steps shall be followed with each
appliance remaining connected to common vent system placed in
operation, while other appliances remaining connected to common
vent system are not in operation:
1. Seal any unused openings in common vent system.
2. Visually inspect vent system for proper size and horizontal
pitch. Determine there is no blockage or restriction, leakage,
corrosion, and other deficiencies which could cause an unsafe
condition.
3. Insofar as is practical, close all building doors and windows
and all doors between space in which appliances remaining
connected to common vent system are located and other
spaces of building. Turn on clothes dryers and any appliance
not connected to common vent system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so they
operate at maximum speed. Do not operate a summer exhaust
fan. Close fireplace dampers.
4. Follow lighting instructions and place appliance in operation.
Adjust thermostat so appliance operates continuously.
5. Test for flue gas spillage at drafthood relief opening after 5
minutes of main burner operation. Use flame of a match or
candle, etc.
6. After it has been determined that each appliance remaining
connected to common vent system properly vents when tested
as above, return doors, windows, exhaust fans, fireplace
dampers, any other gas burning appliances to their previous
condition of use.
7. If improper venting is observed during any of above tests,
common vent system must be corrected. Vent system or vent
connectors may need to be resized. For any other appliances
when resizing vent systems or vent connectors, system or
connector must be sized to approach minimum size as
determined using appropriate table found in Part 11 of NFGC
or Section 5 of NSCNGPIC.
A93053
Step 2—Combustion-Air and Vent Piping
GENERAL
Combustion-air and vent pipe fittings must conform to American
National Standards Institute (ANSI) standards and American
Society for Testing and Materials (ASTM) standards D1785
(schedule-40 PVC), D2665 (PVC-DWV), D2241 (SDR-21 and
SDR-26 PVC), D2661 (ABS-DWV), F628 (schedule-40 ABS), or
F891 (PVC-DWV cellular core). Pipe cement and primer must
conform to ASTM standards D2564 (PVC) or D2235 (ABS). See
Table 5 for maximum pipe lengths and Fig. 31, 32, 33, 34, and 35
for exterior piping arrangements.
In Canada construct all combustion-air and vent pipes for this unit
of CSA or ULC certified schedule-40 PVC, PVC-DWV or
ABS-DWV pipe and pipe cement. SDR pipe is NOT approved in
Canada.
NOTE: Furnace combustion-air and vent pipe connections are
sized for 2-in. pipe. Any pipe size change should be made outside
furnace casing in vertical pipe. (See Fig. 27.) This allows proper
drainage of vent condensate.
Combustion-air and vent pipes must terminate together in same
atmosphere pressure zone, either through roof or sidewall (roof
termination preferred), using accessory termination kit. See Table
4 for required clearances.
Furnace combustion-air and vent pipe connections must be at-
tached as shown in Fig 28. Combustion-air intake plug fitting and
inducer housing alternate vent cap may need to be relocated in
some applications.
20

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

58mvp10058mvp04058mvp060

Table of Contents