Weather station
GIRA
Info
Installation Instructions
Installation
Snap the device onto a 35 x 7.5 top hat rail as per EN
50022.
For operation, the 4-channel analog input needs an
external 24 V power source, e.g order no. 1024 00.
This source can additionally supply the connected
sensors as e.g. WS 10W, WS 10R, the combination
sensor or their heatings.
Prior to switching on the voltage, plug on the terminal
block for the connection of a combination sensor,
even if no such sensor is used.
Connection
+U
:
power supply of external transducers
s
GND:
ref. potential for +U
K1...K4
K1 ... K4:
measured-value inputs
EIB:
EIB connecting terminal
24 V AC:
external power supply voltage
(A):
programming key
(B):
programming LED
(C):
status LED, three-colour
(red, orange, green)
(D):
transducer
(E):
system connector, 6-pole,
for future extensions
(F):
connecting terminal, 4-pole,
for combination sensor
(wind, rain, brightness, twilight)
Weather station
The terminal block for the connection of the com-
bination sensor must be plugged on before the
mains voltage is switched on and during opera-
tion to prevent the digital input from unintention-
al contact with live wires. This would endanger
the safety of the entire system.
As a result, the device and any connected sen-
sors may be irreparably damaged.
Wiring diagram